Page 32
USER MANUAL ref 9011509-01
AFO485 and RFO485
CHARACTERISTICS
Dimensions
115 x 48 x 97 mm (h, l, d)
E.M.I.
EN50082-2 / EN61000-4-5
Electrical security
EN 60950
Protection
IP30
Power supply /
consumption
Double DC power supply 9 to 40 VDC
AFO485 : 170 mA /24 VDC – RFO485 : 250 mA / 24 VDC
Operating temp.
0°C/ + 60°C dry air
RS232
Non isolated
Asynch. 7 or 8 bits + 1 start, 1 or 2 stops
Parity : none / even / odd
1,2 to 115,2 kb/s
RS485 / RS422
Non isolated – Integrated polarisation
Asynch
.
7 or 8 bits + 1 start, 1 or 2 stops
Parity : none / even / odd 1,2 to 115,2 - 93,5 - 187,5 - 500 -
1500 kb/s
Fieldbus
PROFIBUS DP, MODBUS, UNITELWAY, DH-485,
SYSMAC-WAY,
CAN OPEN ISO-DIS-11898
Configuration
By switch
Type of fibre optic
Multimode G50/125 or G62,5/125
Single mode E10/125
Reception fibre and Emission fibre
Optical connector
ST
Modulation
Online data coding
Alarm
Voltage free alarm contact:
Point to point :
Open when the unit is no longer receiving
power or if there is a reception failure.
Bus topology:
Open when a carrier failure has been
detected on any TX or RX F.O. connected to the repeater.
Ring topology /« ring master» repeater:
Open when a
carrier failure has been detected on any F.O. of the ring.
Ring topology / any repeater:
Open when a carrier failure
has been detected on any TX or RX F.O. connected to the
repeater
.