Page 18
USER MANUAL ref 9011509-01
AFO485 and RFO485
3.4. Micro-switches
SWITCHES 1 and 2 : TYPE OF NETWORK
switches
1 2
Large failsafe ring / master
OFF
OFF
Small failsafe ring / master
OFF
ON
Multidrop (= bus repeater)
Failsafe ring / slave
ON OFF
Reserved ON
ON
SWITCH 3 : REGENERATION of CHARACTERS
switch
3
The bytes are not regenerated by passing through the repeater
OFF
The bytes are regenerated when passing through the repeater
ON
SWITCH 4 : FORMAT ON THE ASYNCHRONOUS LINK
RS232, RS485 OR RS422
switch
4
8 bits + parity
1 start + 1 stop
OFF
8 bits without parity or
7 bits + parity
1 start + 1 stop
ON
SWITCHES 5 to 8 : RS232 RS485 RS422DATA RATE
5 6 7 8
Profibus DP
1.5 Mb/s
OFF
ON
OFF
OFF
Profibus DP
500 Kb/s
OFF
ON
OFF
ON
Profibus DP
187 500 b/s
OFF
ON
ON
OFF
115 200 b/s
ON
OFF
OFF
OFF
Profibus DP
93 750 b/s
OFF
ON
ON
ON
57 600 b/s
ON
OFF
OFF
ON
38 400 b/s
ON
OFF
ON
OFF
19 200 b/s
ON
OFF
ON
ON
9 600 b/s
ON
ON
OFF
OFF
4 800 b/s
ON
ON
OFF
ON
2 400 b/s
ON
ON
ON
OFF
1 200 b/s
ON
ON
ON
ON