background image

South Bend, Indiana USA 

 |

  networketi.com

FPT-130 INSTALLATION MANUAL  |  

PART NO. 

25165

 REV 

F

8

OPERATION

The FPT 130 can maintain temperatures at setpoints of 

r)r)r)RUr)ŧr&r&r&RU

10 °C). The heater will energize when the temperature 

drops below the designated setpoint. The heater will de-

energize when the temperature reaches 2 °F (1 °C) above 

the setpoint.

The FPT 130 features ETI’s patented self–testing GFEP, 

which switches the system off when it detects excessive 

ground current leakage (unless Fire Protection Mode is 

on). The GFEP eliminates the extra expenses associated

with having to provide external GFEP.

The FTP 130 also features a Low Current Alarm, which 

switches the system off when it detects a load current 

below 0.1 amps (unless Fire Protection Mode is on). The 

load current is checked during each ground fault test, 

and whenever the load is on. Note: the low-current alarm 

WDNHVƓYHVHFRQGVRIORZFXUUHQWWRDFWLYDWH

FPT 130 Front Panel

Indicator Lights (See Figure 8.)

•  POWER indicator – This green LED lit solid indicates that 

the FPT 130 is receiving power.

  –  Blinking indicates a calibration error.
•  HEAT indicator – This yellow LED lit solid indicates when 

the heater is energized.

  –  Blinking asymmetric (1/2 sec off × 1–1/2 sec on) – Low  

  Current Alarm, heater relay closed.

  –  Blinking asymmetric (1/2 sec on × 1–1/2 sec off) – Low  

  Current Alarm, heater relay open.

  –  Blinking fast – Stuck relay.
• LOW TEMP indicator – This blue LED lit solid indicates 

when the temperature falls to 32 °F (0 °C) for all 

setpoints except the 30 °F (-1.1 °C) setpoint. For the 30 

°F (-1.1 °C) setpoint the LOW TEMP alarm will indicate 

when the temperature drops to 28 °F (-2.2 °C).

  –  Blinking indicates sensor fault.
  –  Blinking fast – indicates High Temperature alarm.

• ALARM indicator – This red LED lit solid indicates when 

there is a high ground fault current.

  –  Blinking indicates a GFEP circuit failure (this light will  

  also blink while system is preforming a self–test).

Pushbuttons

• TEST/RESET pushbutton – This red pushbutton has the 

following functions:

  – To test the ground fault detector circuit itself AND  

  to test for a ground fault when the heat load is not  

  energized (the heater will energize during the test).  

  Note: whenever the heat is on, the unit is continuously  

  checking for a ground fault.

  –  To reset the system after a ground fault. If the ground  

  fault no longer exists, then normal operation will resume.

  –  To reset the low-current alarm. If the load current is  

 VWLOOEHORZDPSVWKHQWKHDODUPZLOOUHFXULQƓYH

 

 VHFRQGV 1RWH WKH ORZFXUUHQW DODUP WDNHV ƓYH

 

  seconds of low current to activate.

  –  Energizes heater for system testing or troubleshooting.  

 3UHVVLQJWKLVSXVKEXWWRQIRUƓYHVHFRQGVZLOOHQHUJL]H

 

 WKH KHDWHU IRU ƓYH PLQXWHV 3UHVVLQJ WKH SXVK

 

  button again will de-energize the heater and resume  

 normal operation.

Note:

 Because the unit has no ON/OFF power switch, 

power runs to the unit as soon as facility power is 

connected to it. When the unit has power, the green 

POWER indicator will be lit.

FIGURE 8. FPT 130 front panel

POWER

HEAT

LOW TEMP

ALARM

TEST / RESET

FPT 130

HEAT TRACE CONTROL

Heat Tracing Sales        Mt. Airy, MD        (410) 795-2223        www.heattracingsales.com

Heat Tracing Sales        Mt. Airy, MD        (410) 795-2223        www.heattracingsales.com

Содержание Tracon FPT-130

Страница 1: ...se with Inductive loads Inductive loads may create nuisance tripping of the Ground Fault Equipment Protection circuit Utilisation de charge r sistive uniquement Ce produit n est pas destin tre utilis...

Страница 2: ...s la terre doivent toujours tre utilis s pour r duire les risques de choc et d incendie et prot ger l quipement Le c blage lectrique des l ments chauffants doit tre install conform ment aux exigences...

Страница 3: ...round Fault Equipment Protection with manual and automatic test function Alarms for excess ground fault current low load current and temperature Alarms indicated with panel LED lights and relay contac...

Страница 4: ...he hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cable JODQGV 2QH RI WKHVH WWLQJV LV IRU WKH WHPSHUDWXUH VHQVRU cable and the othe...

Страница 5: ...r provides dual Form A DPST contacts rated for heater loads up to 30 amps and 277 volts ac The dual contacts on the contactor are used to control both legs of the input power Line and Neutral Manual L...

Страница 6: ...the COM terminal If the system needs a contact to close to signal an alarm or power off condition connect the other alarm relay lead to the NC Normally Closed terminal See Figure 6 If the system need...

Страница 7: ...up If any DIP switch is changed while the unit is on then the power needs to be turned off and on again for the new setting to take effect FPT130 Thermistor Fault FPT130 Set Point GPT Heat On Fire Pro...

Страница 8: ...tpoints except the 30 F 1 1 C setpoint For the 30 F 1 1 C setpoint the LOW TEMP alarm will indicate when the temperature drops to 28 F 2 2 C Blinking indicates sensor fault Blinking fast indicates Hig...

Страница 9: ...KH EXWWRQ DW this point The unit will exit Manual Mode Note 7KH EOXH PD DVK IRU D FRXSOH RI VHFRQGV after releasing the red TEST RESET pushbutton The blue LED will indicate whether the LOW TEMP Alarm...

Страница 10: ...e setpoint Low current alarm delay 5 s Ground fault limit current 30 mA Self Test Interval 24 h User Interfaces Pushbuttons Test Reset DIP switches Temperature setpoint Thermistor fault mode Fire prot...

Страница 11: ...ion clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about replacement parts or for a replacement Da...

Отзывы: