South Bend, Indiana USA 

 |

  networketi.com

FPT-130 INSTALLATION MANUAL  |  

PART NO. 

25165

 REV 

F

9

DISABLING THE LOW TEMP ALARM LED 

The blue LOW TEMP alarm LED indicates the presence of 

Low Temperature, High Temperature, or a bad thermistor. 

When disabled this blue LED will only indicate for the 

presence of a bad thermistor.

How To Disable The Low Temp Alarm LED

• Hold down the red TEST/RESET pushbutton for 

approximately ten seconds.

 Ŋ$IWHUWKHƓUVWƓYHVHFRQGVWKHXQLWZLOOJRLQWR0DQXDO

 

  Mode, energizing the heater cable if it is not all ready  

 energized.

 Ŋ$IWHUWKHVHFRQGƓYHVHFRQGVWKHXQLWZLOOHQWHUWKH

 

  LOW TEMP blue LED edit mode. This is indicated by  

 WKHEOXH/('ŴDVKLQJUDSLGO\5HOHDVHWKHEXWWRQDW

 

  this point. (The unit will exit Manual Mode.)

 

Note:

7KHEOXH/('PD\ŴDVKIRUDFRXSOHRIVHFRQGV

after releasing the red TEST/RESET pushbutton.

• The blue LED will indicate whether the LOW TEMP 

Alarm is currently disabled or not.

  –  If the blue LED remains on the LOW TEMP Alarm is  

 currently enabled.

  –  If the blue LED goes off the LOW TEMP Alarm is  

 currently disabled.

 Ŋ7RNHHSWKHVHWWLQJDVLWLVZDLWƓYHVHFRQGVDQGWKH

 

  unit will resume normal operation.

  –  To change this setting press the red TEST/RESET  

 SXVKEXWWRQ ZLWKLQ ƓYH VHFRQGV 7KH QHZ VWDWXV RI

 

  this setting will show for three seconds before the unit  

  resumes normal operation.

 

Note:

 7KH EOXH /(' ZLOO ŴDVK UDSLGO\ EHIRUH H[LWLQJ

the LOW TEMP blue LED editing mode and resuming 

normal operation.

Heat Tracing Sales        Mt. Airy, MD        (410) 795-2223        www.heattracingsales.com

Heat Tracing Sales        Mt. Airy, MD        (410) 795-2223        www.heattracingsales.com

Содержание Tracon FPT-130

Страница 1: ...se with Inductive loads Inductive loads may create nuisance tripping of the Ground Fault Equipment Protection circuit Utilisation de charge r sistive uniquement Ce produit n est pas destin tre utilis...

Страница 2: ...s la terre doivent toujours tre utilis s pour r duire les risques de choc et d incendie et prot ger l quipement Le c blage lectrique des l ments chauffants doit tre install conform ment aux exigences...

Страница 3: ...round Fault Equipment Protection with manual and automatic test function Alarms for excess ground fault current low load current and temperature Alarms indicated with panel LED lights and relay contac...

Страница 4: ...he hub to the conduit system before connecting the hub to the enclosure The unit comes with two installed liquid tight cable JODQGV 2QH RI WKHVH WWLQJV LV IRU WKH WHPSHUDWXUH VHQVRU cable and the othe...

Страница 5: ...r provides dual Form A DPST contacts rated for heater loads up to 30 amps and 277 volts ac The dual contacts on the contactor are used to control both legs of the input power Line and Neutral Manual L...

Страница 6: ...the COM terminal If the system needs a contact to close to signal an alarm or power off condition connect the other alarm relay lead to the NC Normally Closed terminal See Figure 6 If the system need...

Страница 7: ...up If any DIP switch is changed while the unit is on then the power needs to be turned off and on again for the new setting to take effect FPT130 Thermistor Fault FPT130 Set Point GPT Heat On Fire Pro...

Страница 8: ...tpoints except the 30 F 1 1 C setpoint For the 30 F 1 1 C setpoint the LOW TEMP alarm will indicate when the temperature drops to 28 F 2 2 C Blinking indicates sensor fault Blinking fast indicates Hig...

Страница 9: ...KH EXWWRQ DW this point The unit will exit Manual Mode Note 7KH EOXH PD DVK IRU D FRXSOH RI VHFRQGV after releasing the red TEST RESET pushbutton The blue LED will indicate whether the LOW TEMP Alarm...

Страница 10: ...e setpoint Low current alarm delay 5 s Ground fault limit current 30 mA Self Test Interval 24 h User Interfaces Pushbuttons Test Reset DIP switches Temperature setpoint Thermistor fault mode Fire prot...

Страница 11: ...ion clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about replacement parts or for a replacement Da...

Отзывы: