background image

  

10 / 16

i) Select

measure, the display will show the Mains Input Voltage of phase.

By pressing and holding 

, the display will show the total kVA of the system.

By pressing and holding 

, the display will show the total kW of the system.

In Manual Mode 

press together 

and

, the 

LED blink and the display will show the maximum 

Voltage value.

l) Select

measure, the display will show the Load Current of phase.

By pressing and holding 

, the display will show the total kvar of system.

In Manual Mode 

press together 

and

, the 

LED blinks and the display will show the maximum 

Current value.

m) Select

measure, the display will show the ambient temperature.

By pressing and holding 

, the display will show the total working Hours.

In Manual Mode 

press together 

and

, the 

LED blink and the display will show the maximum 

Temperature value.

n) Select

measure, the display will show the Total Harmonic Current Distortion in %.

In Manual Mode 

press together 

and

, the 

LED blink and the display will show the maximum

THD value.

9 - COS

MM

SET-UP AND SENSITIVITY SET-UP:

9.1  Cos

M

set-up:

Press the button 

until the LED

turns ON.

Press the button 

to increase the value or the button 

to decrease the value.

The LED

ON indicates that the instantaneous Cos

M

of the installation is inductive.

The LED

ON indicates that the instantaneous Cos

M

of the installation is capacitive.

9

.

2  Sensitivity:

This value refers to the time that unit takes to measure the average Cos

M

of the installation and do the necessary actions on 

the capacitors relays.

The unit of sensitivity is: sec/kvar (The kvar of the lowest capacitor programmed on 

3

.

).

>

Press the button 

until the 

LED lights ON.

>

Press the button 

or 

to modify the value of sensitivity programmed.

>

The time needed to turn ON the step relay depends on the time of Reconnection of the step. (

3

.

).

ETI Elektroelement d.d. - Slovenija

Tel.: 03/56-57-570- Fax: 03/56-74-077

www.eti.si - [email protected]

Содержание 004656570

Страница 1: ...Y SET UP Pg 9 10 OPERATION MODE Pg 9 11 ALARMS TABLE Pg 10 12 TECHNICAL DATA Pg 11 13 TERMINAL CONNECTIONS Pg 15 14 DIMENSIONS Pg 15 AVAILABLE OPTIONAL COMMUNICATION MODULE PC USB RS485 TTL ORDER CODE...

Страница 2: ...cept possible errors deriving from ageing of electronic components By the mean of particular devices and algorithms the instrument controls even electric lines with an high harmonic contents By calcul...

Страница 3: ...ram Q1 The installer has to provide an external disconnection device this breaker has to be easily reachable and identified as disconnection device The value has to be calculated according to the T1 u...

Страница 4: ...means you need to set the value of the primary CT a Press the button to show the parameters value 3 b Press the button to show the parameters value c Press the button to increase or the button to decr...

Страница 5: ...eans the alarm relay normally energized that is closed contact in the absence of alarm Pressing again the function is inverted and display show 1R 5 2 ENTER THE ADVANCED MENU a The controller must be...

Страница 6: ...Modbus 4800 Bds EVEN 1 Bit Stop 4 Modbus 2400 Bds EVEN 1 Bit Stop 5 Modbus 1200 Bds EVEN 1 Bit Stop 6 Modbus 19200 Bds ODD 1 Bit Stop 7 Modbus 9600 Bds ODD 1 Bit Stop 8 Modbus 4800 Bds ODD 1 Bit Stop...

Страница 7: ...or to enter in alarm s parameter shows the G X p Press the button for to enter for set the value q Press the button to increase or the button to decrease the value r Press the button for to enter in a...

Страница 8: ...ORD Default password is and not active as default a The controller must be set on MANUAL operation and all capacitors must be OFF b Press the button for 5 seconds c The display will show 6 7 d The LED...

Страница 9: ...e decimal point on first digit from left is flashing this is because the system working as Generator and the sense of current is inverted verify correct CT connection or modify parameter b Press the b...

Страница 10: ...play will show the Total Harmonic Current Distortion in In Manual Mode press together and the LED blink and the display will show the maximum THD value 9 COSM M SET UP AND SENSITIVITY SET UP 9 1 CosM...

Страница 11: ...eps to be examined 4 If the last step is programmed as Alarm relay then the relay can not be driven manually Note During Manual operation the device controls the reconnection time of the capacitors sa...

Страница 12: ...perature 10sec The temperature refers to set value Display 27 alternated with CosM value 7 THD I 5sec When the THD is higher than the value set on par 7 alternated with THD 36 Set up parameters error...

Страница 13: ...10A 10A Insulating Category Rated Voltage VDE0110 C 250 B 400 C 250 B 400 Maximum Switching Voltage 250V 250V Electrical Contact Life 20 x 106 ops 20 x 1006 ops Mechanical Contact Life 100 x 103 ops 1...

Страница 14: ...MODEL The 96x96 picture shows the TTL version optional 14 DIMENSIONS 96x96 MODEL FRONT VIEW SIDE VIEW PANEL HOLE 144x144 MODEL FRONT VIEW SIDE VIEW PANEL HOLE ETI Elektroelement d d Slovenija Tel 03...

Страница 15: ...ean the device with a soft cloth dampened with water This operation must be done with the instrument switched off and disconnected from any power source ETI Elektroelement d d Slovenija Tel 03 56 57 5...

Страница 16: ...16 16 ETI Elektroelement d d Slovenija Tel 03 56 57 570 Fax 03 56 74 077 www eti si eti eti si...

Отзывы: