Alarm Set-up Menu:
PARAMETER
Description
Range Enable
HH
.
11%
(default)
Range value
GG
.
WW
.
(default)
Range time
GG
.
88
.
(default)
Range Dis. Steps
GG
.
(default)
$$
.
++8
Too High Voltage
0 ... 1 (1)
1 ... 240 (15)
Min/Sec (Min)
0 ... 1 (1)
$$
.
OO8
Too Low Voltage
0 ... 1 (1)
1
…
240 (5)
Min/Sec (Sec)
0 ... 1 (0)
$$
.
++,
Too High Current
0 ... 1 (1)
1
…
240 (2)
Min/Sec (Min)
0 ... 1 (0)
$$
.
//,
Too Low Current
0 ... 1 (1)
1
…
240 (5)
Min/Sec (Sec)
0 ... 1 (1)
$$
.
++&
Over Compensation
0 ... 1 (1)
1
…
240 (2)
Min/Sec (Min)
0 ... 1 (0)
$$
.
//&
Under Compensation
0 ... 1 (1)
1
…
240 (15)
Min/Sec (Min)
0 ... 1 (0)
$$
.
RR7
Over Temperature
0 ... 1 (1)
1
…
600 (10)
Min/Sec (Sec)
0 ... 1 (0)
$$
.
77+
THD % I
0 ... 1 (1)
1
…
240 (3)
Min/Sec (Sec)
0 ... 1 (1)
$$
.
&&6
Low Cos
M
0 ... 1 (1)
1
…
240 (60)
Min/Sec (Sec)
0 ... 1 (0)
PARAMETER
DESCRIPTION
HH
.
11%
Enable alarm: if a 1 = Enable, if a 0 = Disable.
GG
.
WW
.
Delay value before the activation of the alarm relay or before the alarm being shown on display.
GG
.
88
.
Select Min = Minutes or Sec = Seconds time unit that will take the value
GG
.
WW
.
GG
.
On alarm, disconnect steps: if a 1 = Enable, if a 0 = Disable.
6 - SETTING PASSWORD:
Default password is
and not active as default.
a) The controller must be set on MANUAL operation and all capacitors must be OFF.
b) Press the button
for 5 seconds.
c) The display will show
6(7
d) The LED
and
will flash with intermittent of 500ms.
e) Press the button
for 10seconds until display will show
6
.
36
f) To change password value press
or
.
g) To save new password press
for 5 seconds until display will show
6$8
h) To exit without save password press
when password value is show.
i) Now you can view but not modify the parameters.
l) When you try to change the parameters the display show
3$6
, then pressing the keys
or
set the password
and confirm by pressing
m) If the password is correct you have access to edit parameters. After 5 minutes everything will relock again.
n) If the password is incorrect the display shows
(55
.
o) When the instrument requires the password, you have 30secs to enter it, otherwise the system will return to the normal
operation.
p) To disable the password set the value
, or in extreme cases carry out reset (5.3 - Set Default Parameters).