Note! EACH JOB SHOULD BE SIZED ACCORDING TO THE DESIRE OF DEMAND.
Pump size for commerical application when using Eternal as heat engine to recover storage tank
.
FOR GU195(S) ONLY
Pipe Size for Single / Multiple Unit(s) Installation
Number of Eternal
Recommended Pipe Size (mm) Recommended Pipe Size (inch)
1
20
3/4
2
32
1 1/4
3
40
1 1/2
4
50
2
5
50
2
6
50
2
7
65
2 1/2
8
65
2 1/2
Number of Eternal
Minimum Pump Size
Maximum Pump Size
1
5 GPM @25ft head
10 GPM @ 50ft head
2
10 GPM @25ft head
20 GPM @ 50ft head
3
15 GPM @25ft head
20 GPM @ 55ft head
4
15 GPM @30ft head
20 GPM @ 60ft head
Recovery Pump Size
Water Pipe Size
*
For information regarding GU145S or more than 4 units application please contact our service information center.
Note! EACH JOB SHOULD BE SIZED ACCORDING TO THE DESIRE OF DEMAND.
□
Pump must be controlled by aquastat set at least 20
°
F below eternal's setting temperature.
To ensure faster recovery speed, S model is recommended rather than using M model to eliminate staging delay.
□
NOTICE - Recovery Pump
!
!
When using aquastat as pump control in storage tank recovery application, temperature detection may be
insensitive if the aquastat is positioned in a immersion well or sits on the pipe. It is important to check against
eternal's inlet temperature by using eternal's diagnostic function to verify that the pump does shut off when "I"
reached 20
°
F below the setting temperature and aquastat is setup properly.
WARNING - Aquastat
!
!
Содержание GU145 (S)
Страница 5: ...5 Dimensions GU145 S 508 11 12 21 22 1145 S GU195 S M 508 11 12 21 22 1195 S M ...
Страница 6: ...6 Parts Diagram for Model GU145 S 508 11 12 21 22 1145 S GU195 S M 508 11 12 21 22 1195 S M ...
Страница 7: ...7 Parts Diagram for Model GU145 S 508 11 12 21 22 1145 S ...
Страница 50: ...50 DIAGNOSTICS Before calling for service review the following diagnostic steps rst for saving time and money ...
Страница 56: ...56 Wiring and Connection Diagram Wiring Diagram MODEL GU195 M 508 11 12 21 22 1195 M ...