ETC Installation Guide

Dual Tech Wall-mount Occupancy Sensor

Dual Tech Wall-mount Occupancy Sensor

 Page 7 of 8

ETC

5:

Walk Test mode automatically exits and the sensor returns to normal 
operation after five minutes. You can also manually terminate by 
pressing the [Walk Test] button again.

Verify Vacancy Operation

For systems that have been configured for the installed sensor to control 
specific lighting circuits, Walk Test mode can also be used to verify vacancy 
operation.

1:

Confirm the installing technician has programmed the lighting control 
system.

2:

Enable Walk Test mode using the instructions provided in the previous 
section (see 

Walk Test

 on 

page 6

).

3:

With Walk Test mode enabled, exit the room for 15 seconds to allow 
the 10 second timer to expire.

4:

Re-enter the room and confirm the configured vacancy / no occupancy 
state was properly recalled.

5:

Walk Test mode will automatically exit after five minutes from the time 
it was enabled. To manually exit the Walk Test mode, press either of 
the buttons on the sensor.

Sensor Coverage

Narrow Lens

(100ft)

(100ft)

30.5m

30.5m

18.3m

18.3m

(60ft)

(60ft)

2.2m

2.2m

(7ft)

(7ft)

1m

1m

(3ft)

(3ft)

2.1m

2.1m

(6.8ft)

(6.8ft)

3m

3m

(10ft)

(10ft)

10.7m

10.7m

(35ft)

(35ft)

6.56°

6.56°

2.5m

2.5m

(8ft)

(8ft)

0

CL

77°

77°

29°

29°

21.5°

21.5°

14°

14°

5m

5m

(16ft)

(16ft)

5m

5m

(16ft)

(16ft)

2.5m

2.5m

(8ft)

(8ft)

Top View

Side View

Содержание Unison Paradigm

Страница 1: ...accommodate wide or narrow angle spaces The sensor is available in white black or cream finish Configuration The Paradigm Architectural Control Processor P ACP to which this Dual Tech Wall mount Occup...

Страница 2: ...ith a maximum of 90 non condensing humidity Installation ETC recommends paying special attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed v...

Страница 3: ...he following parts and supplies are included with the sensor mounting bracket with pre routed LinkConnect pigtail wires mounting screws WAGO wire termination connectors Installation Installation shoul...

Страница 4: ...ing a new WAGO connector for each termination type 3 Orient the mounting plate with the directional arrows in the upright position to the mounting box and secure it in place using the two screws provi...

Страница 5: ...be identified by pressing the Walk Test button and by using the connected Paradigm ACP LonWorks Connections menu Reference the related source documentation either the LightDesigner Online Help System...

Страница 6: ...lk Test feature A red occupancy and green acoustic LEDs will begin to flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including...

Страница 7: ...le Walk Test mode using the instructions provided in the previous section see Walk Test on page 6 3 With Walk Test mode enabled exit the room for 15 seconds to allow the 10 second timer to expire 4 Re...

Страница 8: ...Tech Wall mount Occupancy Sensor Page 8 of 8 ETC Wide Lens 19 4 19 4 0 5m 5m 10m 10m 16ft 16ft 33ft 33ft 5m 5m 10m 10m 16ft 16ft 33ft 33ft 15 3m 15 3m 7 7 m 7 7 m 4 6m 4 6m 1 7m 1 7m 50ft 50ft 25ft 25...

Отзывы: