ETC Installation Guide

Dual Tech Wall-mount Occupancy Sensor

Dual Tech Wall-mount Occupancy Sensor

 Page 4 of 8

ETC

1:

Pull the Belden 8471 (or equivalent) and one 14 AWG (2.5 mm

2

ground wire to the mounting location (switch box or surface) and strip 
each wire 3/8” (9-10 mm).

2:

Connect the LinkConnect pigtail wires from the mounting bracket to 
the installed wall wires.

a: Connect the data - (typically black) LinkConnect wire from 

mounting bracket to the incoming LinkConnect (typically black) 
wire using a WAGO wire termination connector.

b: Repeat the above steps for the data + (typically white) 

LinkConnect wire and for the ESD ground wire, using a new 
WAGO connector for each termination type.

3:

Orient the mounting plate, with the directional arrows in the upright 
position, to the mounting box and secure it in place using the two 
screws provided.

4:

Install the wall plate to the mounting plate.

a: Align the top of the wall plate to the mounting plate, angling the 

bottom slightly.

The wall-mount sensor is provided with 
a mounting bracket with pre-routed 
LinkConnect pigtail wires. The sensor 
can be mounted to a switch box or 
finished wall surface.

b: Hook the top of the wall plate to the 

tabs located on the mounting plate.

c: Swing the wall plate down, ensuring 

the neck of the sensor extension and 
wires feed through the opening, until 
the magnets engage.

d: If the wall plate does not fully attach, 

wiggle the bottom of the plate 
until all of the magnets are 
seated properly.

Содержание Unison Paradigm

Страница 1: ...accommodate wide or narrow angle spaces The sensor is available in white black or cream finish Configuration The Paradigm Architectural Control Processor P ACP to which this Dual Tech Wall mount Occup...

Страница 2: ...ith a maximum of 90 non condensing humidity Installation ETC recommends paying special attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed v...

Страница 3: ...he following parts and supplies are included with the sensor mounting bracket with pre routed LinkConnect pigtail wires mounting screws WAGO wire termination connectors Installation Installation shoul...

Страница 4: ...ing a new WAGO connector for each termination type 3 Orient the mounting plate with the directional arrows in the upright position to the mounting box and secure it in place using the two screws provi...

Страница 5: ...be identified by pressing the Walk Test button and by using the connected Paradigm ACP LonWorks Connections menu Reference the related source documentation either the LightDesigner Online Help System...

Страница 6: ...lk Test feature A red occupancy and green acoustic LEDs will begin to flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including...

Страница 7: ...le Walk Test mode using the instructions provided in the previous section see Walk Test on page 6 3 With Walk Test mode enabled exit the room for 15 seconds to allow the 10 second timer to expire 4 Re...

Страница 8: ...Tech Wall mount Occupancy Sensor Page 8 of 8 ETC Wide Lens 19 4 19 4 0 5m 5m 10m 10m 16ft 16ft 33ft 33ft 5m 5m 10m 10m 16ft 16ft 33ft 33ft 15 3m 15 3m 7 7 m 7 7 m 4 6m 4 6m 1 7m 1 7m 50ft 50ft 25ft 25...

Отзывы: