ETC Installation Guide
Dual Tech Wall-mount Occupancy Sensor
Dual Tech Wall-mount Occupancy Sensor
Page 4 of 8
ETC
1:
Pull the Belden 8471 (or equivalent) and one 14 AWG (2.5 mm
2
)
ground wire to the mounting location (switch box or surface) and strip
each wire 3/8” (9-10 mm).
2:
Connect the LinkConnect pigtail wires from the mounting bracket to
the installed wall wires.
a: Connect the data - (typically black) LinkConnect wire from
mounting bracket to the incoming LinkConnect (typically black)
wire using a WAGO wire termination connector.
b: Repeat the above steps for the data + (typically white)
LinkConnect wire and for the ESD ground wire, using a new
WAGO connector for each termination type.
3:
Orient the mounting plate, with the directional arrows in the upright
position, to the mounting box and secure it in place using the two
screws provided.
4:
Install the wall plate to the mounting plate.
a: Align the top of the wall plate to the mounting plate, angling the
bottom slightly.
The wall-mount sensor is provided with
a mounting bracket with pre-routed
LinkConnect pigtail wires. The sensor
can be mounted to a switch box or
finished wall surface.
b: Hook the top of the wall plate to the
tabs located on the mounting plate.
c: Swing the wall plate down, ensuring
the neck of the sensor extension and
wires feed through the opening, until
the magnets engage.
d: If the wall plate does not fully attach,
wiggle the bottom of the plate
until all of the magnets are
seated properly.