ETC Unison Paradigm Скачать руководство пользователя страница 3

ETC Installation Guide

Dual Tech Wall-mount Occupancy Sensor

Dual Tech Wall-mount Occupancy Sensor

 Page 3 of 8

ETC

Control Wire Specification

Wall-mount Occupancy Sensors connect to the LinkConnect station 
communication bus. LinkConnect is a bidirectional protocol that uses one 
pair of wires (data+ and data-) for both data and power. ETC recommends 
using Belden 8471 (or approved equal) Class 2 wire. The total combined 
length of a LinkConnect wire run (using Belden 8471, or equal) may not 
exceed 1,640 feet (500 m) with a maximum distance of 1,312 feet (400 m) 
between any two devices.

Parts and Supplies

The following parts and supplies are included with the sensor:

• mounting bracket with pre-routed LinkConnect pigtail wires
• mounting screws
• WAGO (wire termination connectors)

Installation

Installation should follow all local codes and standard electrical practices.

Note: All control wiring should be installed and terminated by 

a qualified installer and should follow standard wiring 

installation practices. Leave approximately 10 inches 

(254 mm) of wiring in the switch box for connection and 

to allow slack for future service needs.

Note: ETC requires that all stations be grounded. Pull an 

additional 14 AWG (2.5 mm

2

) wire for grounding when 

control wires are not installed in grounded metal 

conduit.

Note: NEC Class 2 product to be wired in accordance to NEC 

Article 725 and local jurisdiction requirements.

Содержание Unison Paradigm

Страница 1: ...accommodate wide or narrow angle spaces The sensor is available in white black or cream finish Configuration The Paradigm Architectural Control Processor P ACP to which this Dual Tech Wall mount Occup...

Страница 2: ...ith a maximum of 90 non condensing humidity Installation ETC recommends paying special attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed v...

Страница 3: ...he following parts and supplies are included with the sensor mounting bracket with pre routed LinkConnect pigtail wires mounting screws WAGO wire termination connectors Installation Installation shoul...

Страница 4: ...ing a new WAGO connector for each termination type 3 Orient the mounting plate with the directional arrows in the upright position to the mounting box and secure it in place using the two screws provi...

Страница 5: ...be identified by pressing the Walk Test button and by using the connected Paradigm ACP LonWorks Connections menu Reference the related source documentation either the LightDesigner Online Help System...

Страница 6: ...lk Test feature A red occupancy and green acoustic LEDs will begin to flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including...

Страница 7: ...le Walk Test mode using the instructions provided in the previous section see Walk Test on page 6 3 With Walk Test mode enabled exit the room for 15 seconds to allow the 10 second timer to expire 4 Re...

Страница 8: ...Tech Wall mount Occupancy Sensor Page 8 of 8 ETC Wide Lens 19 4 19 4 0 5m 5m 10m 10m 16ft 16ft 33ft 33ft 5m 5m 10m 10m 16ft 16ft 33ft 33ft 15 3m 15 3m 7 7 m 7 7 m 4 6m 4 6m 1 7m 1 7m 50ft 50ft 25ft 25...

Отзывы: