ETC Unison Paradigm Скачать руководство пользователя страница 6

ETC Installation Guide

Dual Tech Wall-mount Occupancy Sensor

Dual Tech Wall-mount Occupancy Sensor

 Page 6 of 8

ETC

• When occupancy in the space has only been triggered by acoustic 

detection for 60 minutes, acoustic detection is disabled until the next 
PIR detection event.

PIR (only) Detection

When acoustic detection is disabled, the following logic is used:

• When the space is vacant, only PIR detection can switch the state to 

occupied.

• When the space is occupied, PIR detection resets the vacancy timeout.

Walk Test

1:

Prepare the site for configuration.

a: Make certain the sensor is powered and bound to the P-ACP.

b: You will need direct access to the sensor in order to place it into 

Walk Test mode.

2:

Press the [Walk Test] button on the bottom of the sensor to enable the 
Walk Test feature. A red (occupancy) and green (acoustic) LEDs will 
begin to flash indicating Walk Test is enabled, and the vacancy timer 
will be shortened to ten seconds.

3:

Move throughout the space including corners and areas that may 
specifically be obscured from line-of-sight to the sensor. Each time the 
sensor detects movement, the lens will illuminate red. If acoustic 
detection is enabled, any sound detected will illuminate the acoustic 
detection LED green.

4:

As needed, adjust the angle of the sensor head to obtain the detection 
in the space.

Note: Walk Test mode is available only when the sensor is 

bound to a P-ACP. Attempting a walk test with an 

unbound sensor causes the sensor walk test LED to blink 

amber continuously, or until the sensor is bound to the 

P-ACP.

[Walk Test] 
button

The sensor offers a Walk Test 
mode, which shortens the 
vacancy timer to ten seconds 
and allows for simple and quick 
verification of the sensor’s 
coverage and range in the 
installed space.

Содержание Unison Paradigm

Страница 1: ...accommodate wide or narrow angle spaces The sensor is available in white black or cream finish Configuration The Paradigm Architectural Control Processor P ACP to which this Dual Tech Wall mount Occup...

Страница 2: ...ith a maximum of 90 non condensing humidity Installation ETC recommends paying special attention to the installation environment When operating in PIR only modes the sensor must have an unobstructed v...

Страница 3: ...he following parts and supplies are included with the sensor mounting bracket with pre routed LinkConnect pigtail wires mounting screws WAGO wire termination connectors Installation Installation shoul...

Страница 4: ...ing a new WAGO connector for each termination type 3 Orient the mounting plate with the directional arrows in the upright position to the mounting box and secure it in place using the two screws provi...

Страница 5: ...be identified by pressing the Walk Test button and by using the connected Paradigm ACP LonWorks Connections menu Reference the related source documentation either the LightDesigner Online Help System...

Страница 6: ...lk Test feature A red occupancy and green acoustic LEDs will begin to flash indicating Walk Test is enabled and the vacancy timer will be shortened to ten seconds 3 Move throughout the space including...

Страница 7: ...le Walk Test mode using the instructions provided in the previous section see Walk Test on page 6 3 With Walk Test mode enabled exit the room for 15 seconds to allow the 10 second timer to expire 4 Re...

Страница 8: ...Tech Wall mount Occupancy Sensor Page 8 of 8 ETC Wide Lens 19 4 19 4 0 5m 5m 10m 10m 16ft 16ft 33ft 33ft 5m 5m 10m 10m 16ft 16ft 33ft 33ft 15 3m 15 3m 7 7 m 7 7 m 4 6m 4 6m 1 7m 1 7m 50ft 50ft 25ft 25...

Отзывы: