1:

Pull DALI ballast control wiring pairs into the Sensor IQ low voltage trough. Reference the 

Sensor IQ 

Installation Manual

 for cable routing and conduit access information.

2:

Strip the insulation back from each wire pair 6 mm (1/4 in).

3:

Using a 3 mm (1/8 in) flatblade screwdriver, loosen the terminals and insert each of the data + and 
data - wire set into the appropriate terminal for the circuit.
• Notice the connector is labeled for your wire termination reference. 

4:

Tighten each screw terminal until the wire is securely held.

5:

Repeat steps 1–4 for the remaining DALI outputs in the panel.
• Connect up to 24 DALI loops per system.

Connect the Wire Harness

1:

Noting connector orientation, plug one end of the wire harness (supplied with the option kit) into 
the option card connector.

2:

Noting connector orientation, plug the second end of the wire harness into one of the option card 
headers found on the circuit board mounted on the inside rear of the panel as shown below.

Remove the Option Card

1:

Use a small pliers to compress the plastic tabs on the mounting pins.

2:

While the tabs are compressed, gently pull the option card away from the panel.

Note:

The associated output loop terminal number should always match the relay circuit number 

inside the relay panel. For example: If relay 1 is connected to a DALI ballast load, control 

wiring would terminate to the IQ-DALI option board output terminals labeled “+ 1 -”.