ETC Installation Guide

Contact and Demand Response Interfaces

the terminal labeled “+”.

4.

Secure the screws firmly onto each wire.

Connect EchoConnect

1.

Strip 9-10 mm (3/8 in) of insulation from the bare end of the Belden
8471 (or equivalent) wires and the ESD ground wire.

2.

Loosen the three screw terminals (ground, -, +) on the EchoConnect
terminals.

3.

Insert the data + wire (white is typical) into the terminal labeled “+”,
insert the data - wire (black is typical) into the terminal labeled “-”, and
insert the ground wire (green/yellow is typical) into the terminal

labeled

.

4.

Secure the screws firmly onto each wire.

Connect Input Wiring (Input Interface and Demand
Response)

Dry Contact Input

1.

Strip 9-10 mm (3/8 in) of insulation from each wire.

2.

Loosen the two terminals (“In” and “V out”).

3.

Insert one wire into each terminal, and then secure the screws firmly
onto each wire.

Wet Contact Input

For a wet contact input into the Contact Input Interface, you must terminate
to both the “In” and the negative “-” terminal of the 24 VDC auxiliary input.
The “V out” terminal will not be used for this termination.

1.

Strip 9-10 mm (3/8 in) of insulation from each wire.

2.

Loosen the “In” terminal for the contact input and insert the po
contact voltage wire.

3.

Terminate the contact return wire into the negative “-” terminal of the
24 VDC input. Alternative wiring termination methods may be
required to accommodate multiple terminations.

4.

Secure the screws firmly onto each wire for all terminals.

Connect Output Wiring (Output Interface only)

1.

Strip 9-10 mm (3/8 in) of insulation from each wire.

2.

Determine the type of output required, normally open (NO) or normally
closed (NC), and then loosen the respective output and COM
terminals.

3.

Insert the common wire into the “COM” terminal and the output wire
into the respective “NO” or “NC” terminal.

4.

Secure the screws firmly onto each wire.

Contact and Demand Response Interfaces

Page 4 of 8

ETC

Содержание Echo Contact Input

Страница 1: ...actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface provides four normally open...

Страница 2: ...of wires data and data for both data and power ETC recommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not...

Страница 3: ...O normally closed N C and common COM for connection of output relays Terminals accept 0 2 mm 2 4 mm 2 24 12 AWG wire Each output includes a corresponding on board LED to indicate the normally open sta...

Страница 4: ...Wet Contact Input For a wet contact input into the Contact Input Interface you must terminate to both the In and the negative terminal of the 24 VDC auxiliary input The V out terminal will not be use...

Страница 5: ...achine driven applications ETC recommends a minimum of 500 ms between any input changes to ensure transitions are reliably applied Demand Response Interface Activates Demand Response affecting up four...

Страница 6: ...owing default behaviors until changed using the EchoAccess App Input Interface Inputs control Presets 1 4 respectively using maintained input mode where closing the contact activates the preset openin...

Страница 7: ...spaces that will be controlled A value higher than 13 will result in control of only Spaces 14 15 and 16 2 Set the Address Zone For a Contact Input Interface set the Address 1 through 16 available whi...

Страница 8: ...cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset button for ten seconds to reset the interface to factory defaults The power...

Отзывы: