background image

ETC Installation Guide

Contact and Demand Response Interfaces

Input and Demand Response Interface Wire Terminations

The Contact Input and Demand Response Interfaces provide four sets of
terminals (“In” and “V out”) for connection to a momentary (Input Interface
only) or maintained contact input. Terminals accept 0.2 mm

2

-4 mm

2

(24-12

AWG) wire. Each input supports wet or dry contact closures and includes a
related on board LED to indicate contact status.

Note:

Input terminals accept 3 - 24 VDC and support 610 m

(2,000 ft) of 1 mm

2

(18 AWG) wire (round trip wire to the device)

when using 24 VDC.

Output Interface Wire Terminations

The Contact Output Interface provides four sets of terminals (normally open
“N.O.”, normally closed “N.C.”, and common “COM”) for connection of
output relays. Terminals accept 0.2 mm

2

-4 mm

2

(24-12 AWG) wire. Each

output includes a corresponding on board LED to indicate the normally open
status of the relay.

Installation

Install to DIN rail

2

3

1.

Ensure the section of DIN rail to be
used is mounted securely
according to the manufacturer’s
requirements. (DIN rail is provided
by others.)

2.

Hook the bottom of the device
under the lower DIN rail edge as
shown.

3.

Pivot the device up and depress
until the top clip seats completely
onto the DIN rail.

Terminate Wiring

Connect Auxiliary 24 VDC

1.

Strip 9-10 mm (3/8 in) of insulation from the end of each wire.

2.

Loosen the two 24 VDC screw terminals.

3.

Insert the negative voltage wire (black wire typical) into the terminal
labeled “-”, and insert the positive voltage wire (red wire typical) into

Contact and Demand Response Interfaces

Page 3 of 8

ETC

Содержание Echo Contact Input

Страница 1: ...actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface provides four normally open...

Страница 2: ...of wires data and data for both data and power ETC recommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not...

Страница 3: ...O normally closed N C and common COM for connection of output relays Terminals accept 0 2 mm 2 4 mm 2 24 12 AWG wire Each output includes a corresponding on board LED to indicate the normally open sta...

Страница 4: ...Wet Contact Input For a wet contact input into the Contact Input Interface you must terminate to both the In and the negative terminal of the 24 VDC auxiliary input The V out terminal will not be use...

Страница 5: ...achine driven applications ETC recommends a minimum of 500 ms between any input changes to ensure transitions are reliably applied Demand Response Interface Activates Demand Response affecting up four...

Страница 6: ...owing default behaviors until changed using the EchoAccess App Input Interface Inputs control Presets 1 4 respectively using maintained input mode where closing the contact activates the preset openin...

Страница 7: ...spaces that will be controlled A value higher than 13 will result in control of only Spaces 14 15 and 16 2 Set the Address Zone For a Contact Input Interface set the Address 1 through 16 available whi...

Страница 8: ...cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset button for ten seconds to reset the interface to factory defaults The power...

Отзывы: