background image

ETC Installation Guide

Contact and Demand Response Interfaces

Set Space and Address / Zone Start

Interface devices participate in an Echo control system using the configured
Space and Address / Zone which are selectable using the rotary switches on
the front of the unit. By default, these switches are set to Space 1, Address /
Zone 1.

1.

Set the Space for this device (1 through 16 available). All control inputs
from the connected stations, sensors, and other controls are shared by
all devices within the selected space. This setting applies regardless of
the selected configuration mode (Basic or Custom).

Note:

For the Demand Response Interface, setting the Space address

determines the four consecutive spaces that will be controlled. A value
higher than 13 will result in control of only Spaces 14, 15, and 16.

2.

Set the Address / Zone:

For a Contact Input Interface, set the Address (1 through 16
available) which identifies the device in the selected space. This
setting always applies.

Note:

Do not duplicate a device address within the same space.

For a Contact Output Interface, set the Zone number (1 through
16 available) for the first output on the interface. The remaining
outputs will be assigned consecutive zone numbers. The zone
number does not apply while in Custom configuration mode.

Note:

When setting the first zone number, be careful to allow

enough in the range for all outputs in the interface. For example, if
you set the first zone to address 15, the remaining output contacts on
the controller will be assigned to and respond as Zone 16.

Contact and Demand Response Interfaces

Page 7 of 8

ETC

Содержание Echo Contact Input

Страница 1: ...actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface provides four normally open...

Страница 2: ...of wires data and data for both data and power ETC recommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not...

Страница 3: ...O normally closed N C and common COM for connection of output relays Terminals accept 0 2 mm 2 4 mm 2 24 12 AWG wire Each output includes a corresponding on board LED to indicate the normally open sta...

Страница 4: ...Wet Contact Input For a wet contact input into the Contact Input Interface you must terminate to both the In and the negative terminal of the 24 VDC auxiliary input The V out terminal will not be use...

Страница 5: ...achine driven applications ETC recommends a minimum of 500 ms between any input changes to ensure transitions are reliably applied Demand Response Interface Activates Demand Response affecting up four...

Страница 6: ...owing default behaviors until changed using the EchoAccess App Input Interface Inputs control Presets 1 4 respectively using maintained input mode where closing the contact activates the preset openin...

Страница 7: ...spaces that will be controlled A value higher than 13 will result in control of only Spaces 14 15 and 16 2 Set the Address Zone For a Contact Input Interface set the Address 1 through 16 available whi...

Страница 8: ...cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset button for ten seconds to reset the interface to factory defaults The power...

Отзывы: