20
CEM3 User Manual
Rack Property Definitions
Each rack has specific properties that dictate how the rack is identified and functions. Edit these
properties in the Rack Setup screen ([Setup]>Rack).
Rack Property
Definition
Rack Number
Select a rack number between 1–999.
System Number
Select a system number between 1–999. Default is 1. Changing the
system number will require a reboot.
DMX A
Enable or disable the DMX A port. When Disabled the respective Priority
field is not visible, and Off is displayed on the home screen. Default for
DMX A is Enabled.
Priority (DMX A)
Visible only when DMX A output is Enabled. Configure the priority of the
DMX A output signal from the rack. Range is between 1–200
(200 = highest priority). Default is 100.
DMX B
Enable or disable the DMX B port. When Disabled the respective Priority
field is not visible, and Off is displayed on the home screen. Default for
DMX B is Disabled.
Priority (DMX B)
Visible only when DMX B output is Enabled. Configure the priority of the
DMX B output signal from the rack. Range is between 1–200
(200 = highest priority). Default is 100.
sACN
Enable or disable the sACN port. When Disabled, Off displays on the
home screen. Default for sACN is Enabled.
Arch Priority
Set the priority used for preset playback. Range is between 1–200
(200 = highest priority). Default is 100.
Off as Release
Select Yes to revert from architectural preset control to DMX or sACN
console control when the Off preset is activated. Select No to maintain
preset control and play the Off preset until you select Release All Arch.
Fan
The length of time (in minutes) the rack fan will stay on after the last load
in the rack has reached 0%. Select a time between 30–180 minutes or
Always-On. Default is 30.
AF Enabled
Set whether Advanced Features (AF) are enabled (Yes/No). Default is
based on the backplane DIP switch setting.
Presets on Boot
If Enabled and the rack is rebooted when a preset (or presets) are active,
those same presets will be reactivated when the rack reboots.
Setup at Home
Set whether Quick Setup is displayed on the home screen. Default is Yes
for portable racks and No for install racks.
Volt High Warn
Set the threshold voltage to report an "over voltage” condition
.
Default is
140VAC for 100–120VAC systems and 250VAC for 230–240VAC
systems.
Temp High Warn
Set the threshold temperature to report an “over temperature”
condition. The range is between 32–158°F (0–70C). Default is 149°F
(65C).
Station Power
Set whether the preset station power supply for this CEM3 is turned on.
Default is Off (see
for more information).
Remote Record
Set whether presets can be remotely recorded from preset stations.
Default is No.
[Data Loss Behavior]
Opens the Data Loss Behavior submenu (see
).
Содержание CEM3
Страница 1: ...Part Number 7140M1200 1 7 0 Rev C Released 2019 04 Sensor3 CEM3 User Manual Version 1 7 0...
Страница 82: ...76 CEM3 User Manual...
Страница 83: ...PhaseAdept Dimmer 77...