CONTROL CARD FEATURES AND SETUP EXPANDED 

A.

 

Auto-close link

: Placing a jumper across these 2 pins will cause the door to close automatically after 20sec. from any 

open position. Before closing the unit will emit three warning beeps. The door can still be triggered to close manually 
before 20sec. has counted down. 

 

B.

 

Receiver programming pins

: Max BT (Button trigger function) = 25 locations. Max L (Light function) = 6 locations.

 

To master erase: (It is recommended that this be done on first time set up) 

1.

 

Remove all power. 

2.

 

Short middle and BT receiver pins and place a wire short  between terminal 3 and 4 (C + BT ) of connector 
block(or press and hold test button “D”) 

3.

 

Re-apply power. Buzzer will begin 1 second beeps. 

4.

 

When buzzer emits 1 continuous tone remove shorts and power. 

5.

 

Re-apply mains power first then battery power. 

 

Programming new Transmitters into memory 

 

1.

 

Press and hold

 required 

TX button

2.

 

While holding

 the 

TX button

 short the middle pin to the required function pin (BT or L) 

3.

 

When buzzer beeps release TX button and remove short.  
1 x Beep - First TX in memory for that function.  

2 x Beeps – There is still memory available for this function. 

10 x Beeps – The last memory location for this function has been filled. Collect all TX’s used for this function 
and check that they are all still working. The last TX learned into this function may have been erased to allow 
your new TX. 

4.

 

Repeat 1 to 3 above for further TX’s. 

 

C.

 

RX detection L.E.D. This will flicker whenever there is a Keeloq transmission present on 433.92 MHz. Non Keeloq formats 
will not activate this L.E.D. Also used as visual confirmation in programming of the onboard RX 

 

D.

 

Test Button

: Will operate door as though using a remote button. 

 

E.

 

AC supply Fuse: 

If blown replace with a 2A fast blow fuse only. (Minimises control card damage in cases of power 

surges or electrical spikes)

 

 
 
F.

 

Load sensing P.O.T

: Used to adjust the amount of obstruction sensitivity necessary to initiate the automatic safety 

routine.  

NB! The ET BLUE ROLL automatically sets its own opening load sensing off the closing setting. When adjusting 

the load sensing use the closing direction!

 

 

When closing, the door will stop and reverse on sensing an obstruction. When opening the door will stop and wait 
for the next trigger to reverse. Turn clockwise to make the operator less sensitive to obstructions. To test place a 
40mm high object below the door when closing. On encountering the object door should return to the open 
position without excessive strain to the door or obstruction object.  

G.

 

Charger Voltage P.O.T: 

This has been set in the factory to 27 – 27.2 Volts without battery load. Do not adjust unless 

qualified to do so. The peak effective current is limited to 370mA. This is a constant voltage, variable current charger 
(Float stage/trickle charger) 

Содержание BLUE-ROLL

Страница 1: ...n Oct 08 002 support et co za Technical specifications may change without prior notice All goods are subject to the standard factory warranty as laid out on the last page of this publication G C Elect...

Страница 2: ...d professional personnel should remove the covers Keep hands and or other parts of the body as well as loose items of clothing clear of the door and operator while operating or servicing In applicatio...

Страница 3: ...it the support bracket or install the drive unit fully inside the drum Fig 7 1 2 Ensure reasonable door condition and operation Before beginning the installation of the opener check the operation of t...

Страница 4: ...to the opposite side of the door from where the opener is to be installed and ensure the U bolts fastening the door shaft to the bracket are firmly tightened Pay extra attention here otherwise the do...

Страница 5: ...s where the unit is installed where it can not be fastened to the door support bracket as in Fig 7 the addition of a self drilling tech screw through the base of the clamp into the torsion bar may be...

Страница 6: ...main purpose is to eliminate the possibility of the door curtain ballooning on initial start up from the door fully open position After installing your new opener if your door balloons on initial star...

Страница 7: ...ing 2 Light cover lens 3 Batteries 4 Control card 5 Transformer behind control card 6 Drive unit cable inlet 7 220V mains cable inlet 8 Antenna 9 Light cover lens fastening screw 10 Main control cover...

Страница 8: ...ARD AS PER FIG 12 OR FIG 13 TO CONTINUE NB The motor wiring of a right hand installation differs to that of a left hand installation Figures 12 and 13 below indicate the wiring requirements for either...

Страница 9: ...LOW 24Vac input from transformer secondary SEC 22 Positive auxiliary output 12V 100mA peak 23 0V auxiliary output Ground Fig 11 A Autoclose jumper On active 20secs and pre beep warning B Receiver prog...

Страница 10: ...10 Fig 12 Left hand installation Fig 13 Right hand installation Red 0 75mm Motor Yellow 0 75mm Motor White 0 3mm Limit common Brown 0 3mm Open limit Green 0 3mm Closed limit...

Страница 11: ...orking The last TX learned into this function may have been erased to allow your new TX 4 Repeat 1 to 3 above for further TX s C RX detection L E D This will flicker whenever there is a Keeloq transmi...

Страница 12: ...new transmitter before the buzzer tone stops If the tone stops before pressing a transmitter button then restart from b d The onboard buzzer will indicate whether or not the programming was successful...

Страница 13: ...t lock the cam to the extent that you can rotate the cam by hand while the cam can not rotate itself Rotate the open limit cam inner cam clockwise by hand in the direction of the limit switch until th...

Страница 14: ...te itself Rotate the open limit cam inner cam anti clockwise by hand in the direction of the limit switch until the cam clicks the open limit switch see Fig 16 9 2 Closed Limit Close the door manually...

Страница 15: ...h no mains power Approximately 5 full cycles 10 7 Call for professional garage door service if necessary 11 We recommend the following service to be carried out ONCE A YEAR 11 1Professional services t...

Страница 16: ...level is less than minimum allowed BT triggered Once every 16sec Anywhere On Charging Will operate Battery charge level is less than minimum allowed and busy charging None In case of any misunderstand...

Страница 17: ...claims must be accompanied by the original invoice All claims made by the end user must be directed to their respective service provider installer The following items are not included in the warranty...

Отзывы: