11
CONTROL CARD FEATURES AND SETUP EXPANDED
A.
Auto-close link
: Placing a jumper across these 2 pins will cause the door to close automatically after 20sec. from any
open position. Before closing the unit will emit three warning beeps. The door can still be triggered to close manually
before 20sec. has counted down.
B.
Receiver programming pins
: Max BT (Button trigger function) = 25 locations. Max L (Light function) = 6 locations.
To master erase: (It is recommended that this be done on first time set up)
1.
Remove all power.
2.
Short middle and BT receiver pins and place a wire short between terminal 3 and 4 (C + BT ) of connector
block(or press and hold test button “D”)
3.
Re-apply power. Buzzer will begin 1 second beeps.
4.
When buzzer emits 1 continuous tone remove shorts and power.
5.
Re-apply mains power first then battery power.
Programming new Transmitters into memory
1.
Press and hold
required
TX button
.
2.
While holding
the
TX button
short the middle pin to the required function pin (BT or L)
3.
When buzzer beeps release TX button and remove short.
1 x Beep - First TX in memory for that function.
2 x Beeps – There is still memory available for this function.
10 x Beeps – The last memory location for this function has been filled. Collect all TX’s used for this function
and check that they are all still working. The last TX learned into this function may have been erased to allow
your new TX.
4.
Repeat 1 to 3 above for further TX’s.
C.
RX detection L.E.D. This will flicker whenever there is a Keeloq transmission present on 433.92 MHz. Non Keeloq formats
will not activate this L.E.D. Also used as visual confirmation in programming of the onboard RX
D.
Test Button
: Will operate door as though using a remote button.
E.
AC supply Fuse:
If blown replace with a 2A fast blow fuse only. (Minimises control card damage in cases of power
surges or electrical spikes)
F.
Load sensing P.O.T
: Used to adjust the amount of obstruction sensitivity necessary to initiate the automatic safety
routine.
NB! The ET BLUE ROLL automatically sets its own opening load sensing off the closing setting. When adjusting
the load sensing use the closing direction!
When closing, the door will stop and reverse on sensing an obstruction. When opening the door will stop and wait
for the next trigger to reverse. Turn clockwise to make the operator less sensitive to obstructions. To test place a
40mm high object below the door when closing. On encountering the object door should return to the open
position without excessive strain to the door or obstruction object.
G.
Charger Voltage P.O.T:
This has been set in the factory to 27 – 27.2 Volts without battery load. Do not adjust unless
qualified to do so. The peak effective current is limited to 370mA. This is a constant voltage, variable current charger
(Float stage/trickle charger)