Network Controllers Manual
19
Jumper Setup
Jumper Setup
Jumper Name
Jumper State
Condition
J3
IN
No option card installed in P5
J3
OUT
Option card installed in P5
J4
IN
No option card installed in P6
J4
OUT
Option card installed in P6
System Configuration
Configuration is dependent upon system requirements and design. All
CM2s have a CM2 CPU card (P/N 130073/1) installed in connector P4.
System communication specifications govern the type of communications
card installed in connector P3 of the CM2. Wiring to CM2 terminal strip
TB1 is dependent on the type of communications card installed, and may
be found on the COMM-3 RS-485/RS-232C communications card (P/N
130080) or the COMM-3S serial communications card (P/N 130144).
Two option cards may be installed in the CM2 in connectors P5 and P6.
Details on option card programming and termination’s of CM2 terminal
strips TB2, TB3, and TB4 may be found on each modules data sheet.
Programming Notes
The CM2 panel configuration menu (menu selection “3”) in the data entry
program should be set as “supervised” power supply. Additional control
modules should be set as “unsupervised” power supply when connected to
the same power supply as the CM1 or another CM2.
Jumper Connections:
Pins 6, 8, and 20
Pins 4 and 5
Jumper Connections:
Pins 1, 4, and 6
Pins 7 and 8
TB1-2
TB1-2
TB1-3
TB1-3
TB1-4
TB1-4
[NWC-004.CDR]
DB25 FEMALE or DB9 FEMALE
Download Cable
TO PC SERIAL PORT
PIN 1
PIN 14
PIN 13
PIN 25
PIN 1
PIN 9
2 3
7
OR
2 3
5
CONTROL PANEL
MOTHER BOARD CM1(N) or CM2(N)
TB1
4
8
10
1
5
3
7
9
2
6
P1
P2
P3
P4
P7
Programming Connections
firealarmresources.com