Parameter 

Word 
address, 
hex 

Data 
type 

Details 

…. 

… 

… 

… 

2 threshold of 16 sensor of 8 
channel card 
(R) 

0х03EF  WORD 

2 threshold = value of this register/10

 

measurement accuracy

in the measurement units of the parameter by 
the sensor 

…. 

… 

… 

… 

Gas type of 1-2 sensor of 
1 channel card 
(R) 

0x0400  WORD 

High byte – odd sensor type code, lower byte 
– even sensor type code (see  Table 10). 

Gas type of 3-4 sensor of 
1 channel card 
(R) 

0x0401  WORD 

High byte – odd sensor type code, lower byte 
– even sensor type code (see  Table 10). 

…. 

… 

… 

… 

Gas type of 7-8 sensor of 
8 channel card 
(R) 

0x043F  WORD 

High byte – odd sensor type code, lower byte 
– even sensor type code (see  Table 10). 

 
Table 2. Concentration and Accuracy (Register Addresses, hex) 

Sensor

 

Channel Card No.

 

End

 

Acc.

 

End

 

Acc.

 

End

 

Acc.

 

End

 

Acc.

 

End

 

Acc.

 

End

 

Acc.

 

End

 

Acc.

 

End

 

Acc.

 

100  101  120  121  140  141  160  161  180  181  1A0  1A1  1C0  1C1  1E0  1E1 

102  103  122  123  142  143  162  163  182  183  1A2  1A3  1C2  1C3  1E2  1E3 

104  105  124  125  144  145  164  165  184  185  1A4  1A5  1C4  1C5  1E4  1E5 

106  107  126  127  146  147  166  167  186  187  1A6  1A7  1C6  1C7  1E6  1E7 

108  109  128  129  148  149  168  169  188  189  1A8  1A9  1C8  1C9  1E8  1E9 

10A  10B  12A  12B  14A  14B  16A  16B  18A  18B  1AA  1AB  1CA  1CB  1EA  1EB 

10C  10D  12C  12D  14C  14D  16C  16D  18C  18D  1AC  1AD  1CC  1CD  1EC  1ED 

10E  10F  12E  12F  14E  14F  16E  16F  18E  18F  1AE  1AF  1CE  1CF  1EE  1EF 

110  111  130  131  150  151  170  171  190  191  1B0  1B1  1D0  1D1  1F0  1F1 

10 

112  113  132  133  152  153  172  173  192  193  1B2  1B3  1D2  1D3  1F2  1F3 

11 

114  115  134  135  154  155  174  175  194  195  1B4  1B5  1D4  1D5  1F4  1F5 

12 

116  117  136  137  156  157  176  177  196  197  1B6  1B7  1D6  1D7  1F6  1F7 

13 

118  119  138  139  158  159  178  179  198  199  1B8  1B9  1D8  1D9  1F8  1F9 

14 

11A  11B  13A  13B  15A  15B  17A  17B  19A  19B  1BA  1BB  1DA  1DB  1FA  1FB 

15 

11C  11D  13C  13D  15C  15D  17C  17D  19C  19D  1BC  1BD  1DC  1DD  1FC  1FD 

16 

11E  11F  13E  13F  15E  15F  17E  17F  19E  19F  1BE  1BF  1DE  1DF  1FE  1FF 

 
Table 3. Sensor State Flags 

Bit Field 

Channel Card No.

 

1 threshold 

200 

206 

20C 

212 

218 

21E 

224 

22A 

2 threshold 

201 

207 

20D 

213 

219 

21F 

225 

22B 

Defect Relay 

202 

208 

20E 

214 

21A 

220 

226 

22C 

1 threshold relay  

203 

209 

20F 

215 

21B 

221 

227 

22D 

2 threshold relay 

204 

20A 

210 

216 

21C 

222 

228 

22E 

Lack of 
communication relay 

205 

20B 

211 

217 

21D 

223 

229 

22F 

 
 
 

Содержание UPES-50D

Страница 1: ...UPES 50D Digital RS485 Multi Channel Controller Operating Manual...

Страница 2: ...gramming Tree Diagrams 18 UPES Menu in the Absence of the channel boards 18 UPES Menu with the Channel Boards Installed 21 UPES Channel Programming 22 UPES Channel Board Com Ports Operation Mode Setti...

Страница 3: ...ctors SGOES TGAES Rx TGAES Tx SSS 903 IPES IR UV IPES IR3 The UPES multi channel controller consists of a control panel capable of connecting up to 16X8 devices via RS485 From 1 to 128 devices can be...

Страница 4: ...unit of BP 10 design 130 242 V 50 Hz main power or direct current with voltage 180 340 V backup power UPES power from DC power supply with voltage not more than V 24 UPES commutated current at AC vol...

Страница 5: ...5 UPES Device Fig 2 UPES Device 1 CPU board 2 8 channel boards with 2 communications lines RS485 3 Power supply unit Fig 2 1 Front View 1 Interconnection board 2 Blind panel 2 3 1 2 1...

Страница 6: ...S ON OFF button 2 LED display 3 Buzzer 4 Keyboard Each channel of the threshold device has a corresponding LED group 2 green Activating 24V at the output of the module 4 red exceeding specified thresh...

Страница 7: ...communication channel it is possible to use any shielded twisted pair cables In this case signal wires are connected to contacts 485 and 485 and the shield is connected to contact GND located at the...

Страница 8: ...connected to each port The state of the sensors connected to the first port is displayed on the first relay set and the state of the sensors connected to the second port on the second relay set The f...

Страница 9: ...displayed on it it immediately turns on threshold LEDs and the threshold relay with the set delay NOTE It is NOT possible to connect on single sensor board gas detectors and flame detectors including...

Страница 10: ...ter ____________________________________________________________________________ 1 channel 2 serial number of the channel board 3 serial number of the sensor connected to the channel board 4 operating...

Страница 11: ...r m a F R E 6 7 C h a n 1 7 7 F i r e F R E C h a n 1 7 7 F a u l t F R E 1 channel 2 serial number of the channel board 3 serial number of the sensor connected to the channel board 4 operating mode o...

Страница 12: ...size of 3U 19 482 266 132 mm built in accordance with the bus structured and modular approach In the frame there is a power supply module CPU module and up to eight two channel modules The power suppl...

Страница 13: ...is indicated by the single sound signal for 1 second Operating Mode Alarms of the Power Supply Indication Mode UPES Power Supply Intermittent green illumination of the UPES power button UPES is not tu...

Страница 14: ...nce of the earthing device that shall not be more than 4 Ohm UPES Installation Clearance Consideration When installing the control panel in a rack there shall be empty space above it and below it that...

Страница 15: ...play The top line displays the channel number and the search percentage completion and in the bottom line displays the search mode Search search all types of sensors in all the MODBUS addresses from 1...

Страница 16: ...arm and relay trigger The LED is faulty Replace the LED The authorized specialist shall perform this operation The threshold is exceeded but external devices are not switched on The relay is faulty Da...

Страница 17: ...oes not switch on All input voltage 220V is lost when the UPES has already been on Connect the power supply to UPES Short term red flashes of the UPES power button no sound signals UPES does not switc...

Страница 18: ...om any menu item without setting the selected value by press the Control Exit button To set the UPES exchange speed with the top level system select the button Prog button of the Exchange rate menu an...

Страница 19: ...19 Figure T1...

Страница 20: ...tors 9600 baud The UPES setup menu is similar to the menu when there are no channel boards fig Error Reference source not found except that if there are channel cards the menu items related to exchang...

Страница 21: ...d whose number is displayed in the top line of the display during the normal operation mode If you want to select the setup menu for the channel board with a different number from the one that appears...

Страница 22: ...press again the Prog button then you get into the channel board setup menu fig T3 Figure T3 In the channel board there are two sets of relays 1 and 2 of the threshold When connecting the channel boar...

Страница 23: ...e second port To select the edited relay kit select Programming Channel x Comp 1 where is the number of the channel being edited To select the second relay set press the or button and the menu Program...

Страница 24: ...and buttons and press the Test Enter button When the sensor threshold is achieved the relay delay triggering can be set by the appropriate threshold to do so it is required to select Relay 1 delay or...

Страница 25: ...t the communication is restored in the initial mode Ring communication with sensors via the first port where the ring integrity is controlled When the ring is open communication between the primary tr...

Страница 26: ...o copy and press the Test Enter button Then press the Prog button and you will enter the set selection menu where to copy the settings Use the or buttons to select the desired channel and the desired...

Страница 27: ...In this menu you can set the sensor search by the known address address search type search by type address and type search by the list or simply search Auto search as well as erase the list of sensor...

Страница 28: ...g button The data about the sensors will be deleted from the channel board memory and the central boards controller will return to the menu title All the thresholds communication failure flags are res...

Страница 29: ...top line contains the number of the channel board in which the search for the sensor will be performed and the ordinal number of the sensor If the channel board is set to the operation mode with two...

Страница 30: ...ensors When you have entered the desired address press the Test Enter button to record the address in memory this address will be in the square brackets To edit the MODBUS address of the next sensor i...

Страница 31: ...e address will be detected automatically The sensors with the None type will not participate in the search The sensor types shall be to filled in starting with the first sensor With the and buttons se...

Страница 32: ...32 Figure T11...

Страница 33: ...g T8 Before you start the search by the list you need to set the list of sensor types and addresses Pressing the Prog button enter the sensor list setup menu The list of sensors is filled in in a mann...

Страница 34: ...modes Setting the necessary number of sensors press the Prog button until the menu appears The search program is started in the same way When the search is complete the display will display the number...

Страница 35: ...T8 and press the Prog button and go to the Search program start menu fig T13 Figure T13 The search program is started in the same way When the search is complete the display will display the number of...

Страница 36: ...bus address 1 247 Device exchange rate R W 0x0001 BYTE Lower byte exchange rate with the top level For the two ports the same rate is set 2 4800 baud 3 9600 baud 4 19200 baud 5 57600 baud 6 115200 bau...

Страница 37: ...wo ports with sensors Setting 8 cards R W 0x000B BYTE High byte communication mode Lower byte exchange rate of two ports with sensors Device identification R 0x000C BYTE Lower byte device model 0 08 H...

Страница 38: ...09 BYTE Measurement accuracy Concentration of 6 sensor of 1 channel card R 0x010A WORD Concentration measured by the sensor Measurement accuracy of 6 sensor of 1 channel card R 0 010B BYTE Measurement...

Страница 39: ...entration measured by the sensor Measurement accuracy of 13 sensor of 1 channel card R 0 0119 BYTE Measurement accuracy Concentration of 14 sensor of 1 channel card R 0x011A WORD Concentration measure...

Страница 40: ...gering of 1 16 sensor of 1 channel card R 0x0201 WORD Triggering flags bit field 0 bit lower 1 sensor 15 bit 16 sensor Defect relay triggering flag of 1 16 sensor of 1 channel card R 0x0202 WORD Trigg...

Страница 41: ...te of the even sensor Units of measurement of 7 and 8 sensor of 1 channel card R 0 0233 BYTE High byte odd sensor units of measurement code lower byte of the even sensor Units of measurement of 9 and...

Страница 42: ...e lower byte even sensor type code Type of 9 10 sensor of 1 channel card R 0x0274 BYTE High byte odd sensor type code lower byte even sensor type code Type of 11 12 sensor of 1 channel card R 0x0275 B...

Страница 43: ...nits of the parameter by the sensor 1 threshold of 2 sensor of 1 channel card R 0 02F1 WORD 1 threshold value of this register 10 measurement accuracy in the measurement units of the parameter by the...

Страница 44: ...166 167 186 187 1A6 1A7 1C6 1C7 1E6 1E7 5 108 109 128 129 148 149 168 169 188 189 1A8 1A9 1C8 1C9 1E8 1E9 6 10A 10B 12A 12B 14A 14B 16A 16B 18A 18B 1AA 1AB 1CA 1CB 1EA 1EB 7 10C 10D 12C 12D 14C 14D 16...

Страница 45: ...ensor Channel Card No 1 2 3 4 5 6 7 8 1 2 2B0 2B8 2C0 2C8 2D0 2D8 2E0 2E8 3 4 2B1 2B9 2C1 2C9 2D1 2D9 2E1 2E9 5 6 2B2 2BA 2C2 2CA 2D2 2DA 2E2 2EA 7 8 2B3 2BB 2C3 2CB 2D3 2DB 2E3 2EB 9 10 2B4 2BC 2C4 2...

Страница 46: ...y Sensors Sensor Channel Card No 1 2 3 4 5 6 7 8 1 2 400 408 410 418 420 428 430 438 3 4 401 409 411 419 421 429 431 439 5 6 402 40A 412 41A 422 42A 432 43A 7 8 403 40B 413 41B 423 42B 433 43B 9 10 40...

Страница 47: ...TO Ethylene oxide 55 DTM Diethylamine 56 IBN Isobutylene 57 HCL hydrogen chloride 58 HF hydrogen fluoride 59 not used Not used 60 MMP methyl mercaptan 61 EMP ethyl mercaptan 62 NAC nitric acid 63 NO n...

Страница 48: ...wer Cable Connection Diagram Wiring Diagrams for Flame Detectors Alterating current from mains 220V 50Hz Contact Mains 1 220V 2 Grounding 3 220V UPES Connector P587 Mains Contact 220V 1 Grounding 2 22...

Страница 49: ...49 Wiring Diagrams for Gas Detectors UPES Markings The UPES device has the following marking manufacturing plant trademark b UPES conventional designation c serial number d year of manufacture...

Страница 50: ...ing shall be performed in accordance with the cyclogram specified in this manual Programming of other UPES parameters shall be also performed in accordance with the cyclogram specified in this OM Prev...

Страница 51: ...uency maintenance check every day maintenance once per quarter technical repair once pert year major overhaul once per 5 years Warranties ESP Safety Inc 555 N First Street San Jose CA 95112 USA guaran...

Отзывы: