31
Search by Type of Sensors
You can search for known type of sensors by selecting (Channel х Search by type) (fig T8).
Selecting this menu item, can press the ("Prog") button to enter the sensor types setup menu (fig
T11).
In the sensor type setting menu the the top line contains the number of the channel board, in
which the search for the sensor will be performed, and the ordinal number of the sensor. If the
channel board is set to the operation mode with two independent ports, the numbering of the
sensors will be not from 1 to 16 but from 1 up to 8 with indication of the port number to which
the sensor is connected, i.e. the top line will look like this ("Channel x-1 P1"), where P1 means
that the sensor is connected to the first port.
In the operation mode with two independent ports in list first there are sensors connected
to the first port from 1 to 8, then to a second port from 1 to 8, the second port would be
designated as («P2») at the upper right part of the UPES screen. The bottom line is "None" and it
means that the type shall be determined, and the sensor MODBUS address equal to zero means
that the address will be detected automatically. The sensors with the «None» type will not
participate in the search.
The sensor types shall be to filled in, starting with the first sensor. With the "+" and "−"
buttons select the sensor type and press the (Test/Enter) button to record this type in the memory,
and then press the ("Prog") key to switch to the next sensor type setting. When you have finished
entering the sensor types, do not change the type of the remaining sensors in the menu, leave
"None" and press the ("Prog") button until you are in the ("Search by Type"). In this menu if
required start the search by type program in the same manner as when searching for the address.
The channel board switches to the search by type mode. The central board controller monitors the
channel board search process and displays the search progress on the UPES display in the same
way when you search for the address.
After finishing the search. the channel board switched to the state and measured
parameters control mode for the found sensors. The UPES display will display the number of the
sensors found.
Search sensors by the types of sensors specified by the operator:
SSS —SSS-903, gas analyzer,
SGO — SGOES-M11, SGOESgas analyzer,
FRE – IPES fire detector,
PGU —primary universal transducer,
SSM– SSS-903МЕ gas analyzer.
TGA – TGAES gas analyzer,