40
Parameter
Word
address,
hex
Data
type
Details
Measurement accuracy of 1
sensor of 2 channel card
(R)
0х0121 BYTE
Measurement accuracy.
….
….
….
…
Concentration of 16 sensor
of 2 channel card
(R)
0x013E WORD Concentration measured by the sensor.
Measurement accuracy of
16 sensor
of 2 channel card
(R)
0х013F BYTE
Measurement accuracy.
…
…
…
…
Flags for 1 threshold
triggering of 1-16 sensor of
1 channel card
(R)
0x0200 WORD
Triggering flags bit field.
0 bit (lower) – 1 sensor, …
15 bit – 16 sensor
Flags for 2 threshold
triggering of 1-16 sensor of
1 channel card
(R)
0x0201 WORD
Triggering flags bit field.
0 bit (lower) – 1 sensor, …
15 bit – 16 sensor
Defect relay triggering flag
of 1-16 sensor of 1 channel
card
(R)
0x0202 WORD
Triggering flags bit field.
0 bit (lower) – 1 sensor, …
15 bit – 16 sensor
Relay triggering flag of
1 threshold of 1-16 sensor
of 1 channel card
(R)
0x0203 WORD
Triggering flags bit field.
0 bit (lower) – 1 sensor, …
15 bit – 16 sensor
Relay triggering flag of
2 threshold of 1-16 sensor
of 1 channel card
(R)
0x0204 WORD
Triggering flags bit field.
0 bit (lower) – 1 sensor, …
15 bit – 16 sensor
Flags of lost communication
with sensor 1–16
of 1 channel card
(R)
0x0205 WORD
Flags bit field.
0 bit (lower) – 1 sensor, …
15 bit – 16 sensor
…
…
…
…