KK-EPA.004 Rev No:0 28.09.18
9
6
.
2 Device Calibration
Press and hold to the PRG key to switch to the programming menu.
6.2.1. Setting the Scale Value
Your device is automatically calibrated to the factory settings and operates in the 0-100 range.
That is, the
smallest value read on the sensor is 0, and the maximum value is 100 on the display.
You can change this
scale on calibration menu.
Use the S-LO for the minimum value displayed on the screen and the S-HI option
for the maximum value.
* After you have set the S-LO value, you can do the same for the S-HI value.
6.2.2 Setting Factor Value
You can use the
Fctor
menu to expand your scale by multiplying it with a fixed factor.The number of this
factor, which is the default value of 1, is multiplied by the values of S-LO and S-HI to determine the scale
value.
For example; When you set the S-LO value to 1, the S-HI value to 20 and make the factor 4, your device will
operate in the range of 4-80 value range.
WARNING:
Changing the scale and factor value does not change the calibration of your device, it only
indicates the displayed value range on the screen.
25
25.
2.5
The decimal point
starts flashing. Use
the UP and DOWN
buttons to select the
decimal digits point.
Press and hold the UP button to
move to the next step. To enter a
negative (-) value, move to one of
the non-digit digits and press the
DOWN button.
When you press and hold
to the PRG key, the value
in the second line starts
blinking. Enter the
desired value using the
UP and DOWN buttons.
2.5
The new S-LO value you confirmed with the PRG key has been
set. Press UP button to move to S-HI.
OUT
S-LO.
0
Cal
I
b
SCALE
Press and hold the PRG button.