- 8 - 

E117.602_En 

 

8. 

Commissioning  

Check that the relay command logic is as required.  

Jumper E1  

E1 positioned towards A 

 

continuous ON command for relay (factory setting) 

 

E1 positioned towards B 

 

relay impulse command (0,5 sec ON every 10 sec)

 

 

Put the power on for the detector, and check that the initial test phase is carried out, which 
includes warming up the sensor, as indicated in the functional status table.  

8.1 

Operating check  

1. 

To  check  that  the  detector  is  working,  simply  push  the  relevant  test  button,  located  inside  the  equipment.    The  alarm 
condition induced by the button activates a functional check of the entire actuation chain, excepting for the sensor, which 
is checked continuously by specific electronic circuitry.  

2. 

Once these tasks have been done, the detector must indicate its alarm status, as follows:  

 

The red LED switches on   

 

The green LED stays on  

 

The buzzer sounds continuously for the entire alarm time.  

 

The relay switches (continuous or impulse) activating any loads connected to it.  

 

The solenoid valve is closed after 15 sec (command impulse for 0,5 sec every 10 sec).  

Once the alarm has ended, the detector automatically returns to normal mode.  

 

It is advisable to repeat the operating test at least once a year, or after a prolonged period of stoppage and 
in any case, every time the detector is replaced.

 

 

CAUTION: The average lifespan of an ESN26.C detector is 6 years, from the date of manufacture.  

 

Test button  

Jumper E1 

Содержание Sensigas ESN26.C

Страница 1: ...v 02 11 12 2018 EsiWelma s r l EW117 602_En Sensigas ESN26 C General instructions Via F lli Canepa 134D E 16010 Serra Ricc Genova Italy Ph 39 010 75421 1 Fax 39 010 75421 78 e mail info esiwelma it We...

Страница 2: ...lectrical signalling devices or activate the solenoid valve to shut off the flow of gas Carbon monoxide is detected by means of an algorithm referred to as integrated threshold which takes into accoun...

Страница 3: ...um 3 metres from the gas operated appliance and at standard face height of the occupants in those premises example 130 170 cm in the kitchen 50 100 cm in the bedroom The detector must not be installed...

Страница 4: ...them scrupulously The device must be installed by qualified technicians 3 Effects of carbon monoxide on the human body Carbon Monoxide CO is a colourless odourless and non irritating gas that is clas...

Страница 5: ...health but the two most important factors are the concentration of CO and the time of exposure to the gas Typical effects of exposure to CO at concentrations and exposure times over the ones that set...

Страница 6: ...connectable in parallel max 9 see wiring diagrams Lifespan of a detector average 6 years from the date of manufacture Max area covered by a detector 40 m approx indicative Visual warnings Green LED po...

Страница 7: ...ower supply Yellow LED warm up and sensor anomaly solenoid valve terminal board for connecting up the solenoid valve terminal board LN for the power supply 230Vac Red LED gas alarm fixing screws cover...

Страница 8: ...characteristics see technical specifications Detectors must be connected directly to the electric relay without disconnectors or switches between them and must be powered permanently 7 Mounting Remov...

Страница 9: ...the entire actuation chain excepting for the sensor which is checked continuously by specific electronic circuitry 2 Once these tasks have been done the detector must indicate its alarm status as foll...

Страница 10: ...entrations of test gases could cause permanent damage to the sensing element and may cause the detector to operate incorrectly 9 Operation Normal Green LED on red and yellow LEDs off Gas alarm Red LED...

Страница 11: ...ioning of the detector and its capacity to activate the alarm due to the presence of gas In order to avoid the yellow LED flashing when the solenoid valve is not in use a suitable load resistance will...

Страница 12: ...and processes that take environmental management into account Refer to the following notes for disposal of the product at the end of its working life or when it is replaced For disposal purposes this...

Страница 13: ...l with other ESN detectors that have a solenoid valve command output e g ESN16 and ESN26 for commanding just one solenoid valve See the wiring diagrams below Diagram 1 ESN26 C detector with N O soleno...

Страница 14: ...26 C detector with N O solenoid valve 230VAC ESN26 C detector air extractor command Y1 N1 L N E V 230V AC N M L LYA26 C NC NO C M1 N1 L N E V 230V AC N L LYA26 C NC NO C K1 N1 ESN26 C N1 ESN26 C Y1 N...

Страница 15: ...9 ESN26 detectors in parallel with N O solenoid valve 12VDC Optional signal buzzer or lamp control Max 9 LYA26 230V AC N L Y1 M N1 L N E V LYA26 NC NO C N9 L N E V LYA26 NC NO C H1 L1 N1 N9 ESN26 Y1...

Страница 16: ...602_En Diagram 5 ESN26 C detector with UZY ALE adapter and N C solenoid valve 12VDC Y1 E V 230V AC N M L U1 L N E V LZY ALE LYA20 N1 L N E V LYA26 NC NO C N1 ESN26 C Y1 N C solenoid valve 12VDC U1 UZ...

Страница 17: ...ALE adapter and N C solenoid valve 12VDC Optional signal buzzer or lamp control Y1 N9 E V 230V AC N M L U1 L N E V LZY ALE LYA20 Max 9 LYA26 N1 L N E V LYA26 NC NO C H1 L1 L N E V LYA26 NC NO C N1 N9...

Страница 18: ...entro il Replace device before 03 2015 14 Dimensions Note Due to our policy of continuous product improvement specifications are subject to change without notice Sensigas ESN26 C Installation date Re...

Отзывы: