6. 

Electrical connections 

 

Conform to current electrical installation norms. 

 

For the connections according to the diagrams in these instructions.  Use cable with a minimum section of 1,5 mm² 

 

Permissible length for connections between detector and solenoid valve: max. 

80 m

 

 

Use solenoid valve output to connect only valves with power absorption not exceeding 13W

 

 

Check that any electrical devices controlled by the relay, are suitable for the maximum capacity characteristics (see 
technical specifications). 

 

Detectors  must  be  connected  directly  to  the  electric  relay,  without  disconnectors  or  switches  between  them,  and 
must be powered permanently. 

7. 

Mounting 

 

Remove the cover by unscrewing the screws on the bottom using a screwdriver. 

 

Fix the base to the wall.  

 

Form the electrical connections as shown in the diagrams contained in this manual.   

 

Fit the cover again, and tighten the fixing screw.  Work carefully to avoid damaging the LEDs. 

 

 

Note: Do not touch the sensing element or the electronic circuit for any reason whatsoever. Any tampering 
may compromise correct functioning of the detector, as well as exposing people to a risk of electric shock.

 

 
 
 

Содержание Sensigas ESN26.C

Страница 1: ...v 02 11 12 2018 EsiWelma s r l EW117 602_En Sensigas ESN26 C General instructions Via F lli Canepa 134D E 16010 Serra Ricc Genova Italy Ph 39 010 75421 1 Fax 39 010 75421 78 e mail info esiwelma it We...

Страница 2: ...lectrical signalling devices or activate the solenoid valve to shut off the flow of gas Carbon monoxide is detected by means of an algorithm referred to as integrated threshold which takes into accoun...

Страница 3: ...um 3 metres from the gas operated appliance and at standard face height of the occupants in those premises example 130 170 cm in the kitchen 50 100 cm in the bedroom The detector must not be installed...

Страница 4: ...them scrupulously The device must be installed by qualified technicians 3 Effects of carbon monoxide on the human body Carbon Monoxide CO is a colourless odourless and non irritating gas that is clas...

Страница 5: ...health but the two most important factors are the concentration of CO and the time of exposure to the gas Typical effects of exposure to CO at concentrations and exposure times over the ones that set...

Страница 6: ...connectable in parallel max 9 see wiring diagrams Lifespan of a detector average 6 years from the date of manufacture Max area covered by a detector 40 m approx indicative Visual warnings Green LED po...

Страница 7: ...ower supply Yellow LED warm up and sensor anomaly solenoid valve terminal board for connecting up the solenoid valve terminal board LN for the power supply 230Vac Red LED gas alarm fixing screws cover...

Страница 8: ...characteristics see technical specifications Detectors must be connected directly to the electric relay without disconnectors or switches between them and must be powered permanently 7 Mounting Remov...

Страница 9: ...the entire actuation chain excepting for the sensor which is checked continuously by specific electronic circuitry 2 Once these tasks have been done the detector must indicate its alarm status as foll...

Страница 10: ...entrations of test gases could cause permanent damage to the sensing element and may cause the detector to operate incorrectly 9 Operation Normal Green LED on red and yellow LEDs off Gas alarm Red LED...

Страница 11: ...ioning of the detector and its capacity to activate the alarm due to the presence of gas In order to avoid the yellow LED flashing when the solenoid valve is not in use a suitable load resistance will...

Страница 12: ...and processes that take environmental management into account Refer to the following notes for disposal of the product at the end of its working life or when it is replaced For disposal purposes this...

Страница 13: ...l with other ESN detectors that have a solenoid valve command output e g ESN16 and ESN26 for commanding just one solenoid valve See the wiring diagrams below Diagram 1 ESN26 C detector with N O soleno...

Страница 14: ...26 C detector with N O solenoid valve 230VAC ESN26 C detector air extractor command Y1 N1 L N E V 230V AC N M L LYA26 C NC NO C M1 N1 L N E V 230V AC N L LYA26 C NC NO C K1 N1 ESN26 C N1 ESN26 C Y1 N...

Страница 15: ...9 ESN26 detectors in parallel with N O solenoid valve 12VDC Optional signal buzzer or lamp control Max 9 LYA26 230V AC N L Y1 M N1 L N E V LYA26 NC NO C N9 L N E V LYA26 NC NO C H1 L1 N1 N9 ESN26 Y1...

Страница 16: ...602_En Diagram 5 ESN26 C detector with UZY ALE adapter and N C solenoid valve 12VDC Y1 E V 230V AC N M L U1 L N E V LZY ALE LYA20 N1 L N E V LYA26 NC NO C N1 ESN26 C Y1 N C solenoid valve 12VDC U1 UZ...

Страница 17: ...ALE adapter and N C solenoid valve 12VDC Optional signal buzzer or lamp control Y1 N9 E V 230V AC N M L U1 L N E V LZY ALE LYA20 Max 9 LYA26 N1 L N E V LYA26 NC NO C H1 L1 L N E V LYA26 NC NO C N1 N9...

Страница 18: ...entro il Replace device before 03 2015 14 Dimensions Note Due to our policy of continuous product improvement specifications are subject to change without notice Sensigas ESN26 C Installation date Re...

Отзывы: