![ESD C.3012.02 Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/esd/c-3012-02/c-3012-02_manual_2426453091.webp)
Device Profile Area
CAN-CBX-REL4
Manual • Doc.-No.: C.3012.21 / Rev. 1.1
Page 91 of 99
7.10.10 Error Value Output Bit 1 to 4 (6260
h
)
On condition that the corresponding error mode (object 6250
h
) is enabled, device errors shall switch the
relays to the error value defined in this object,
Index
Sub-
index
Description
Value range
Default
Data type
Access
6260
h
0
number_of_entries
4
4
unsigned 8
ro
1
error_value_Rel1
0,1
1
Boolean
rw
2
error_value_Rel2
0,1
1
Boolean
rw
3
error_value_Rel3
0,1
1
Boolean
rw
4
error_value_Rel4
0,1
1
Boolean
rw
Assignment of the variable error_value_Relx (x=1...4)
This variable contains the error value.
error_value_Relx
Value
Meaning
true
1
If object 6250
h
is enabled, relay x is energized in case of error.
false
0
If object 6250
h
is enabled, relay x is de-energized in case of an
error.