Technical Data
Manual • Doc.-No.: C.3012.21 / Rev. 1.1 CAN-CBX-REL4
Page 10 of 99
2. Technical Data
2.1 General technical Data
Power supply voltage
nominal voltage:
24 V/DC
input voltage range:
18...30 V/DC
current consumption (24 V, 20
m
C):
approx. 100 mA
Connectors
24V
(4-pin line connector with spring-cage connection, X100) -
24 V-power supply voltage
InRailBus (5-pin CAN-CBX-TBUS, Phoenix Contact, X101) -
CAN interface and power supply voltage via InRailBus
11-44
(10-pin line connector with screw connection, X300) -
Relay outputs (2 monostable change over contacts,
2 monostable normally open contacts)
CAN
(5-pin line connector with spring-cage connection, X600) -
CAN interface
Only for test and programming purposes:
X200
(6-pin connector) - the connector is placed inside the case
Temperature range
-20
m
C ... +70
m
C ambient temperature
Humidity
max. 90%, non-condensing
Protection class
IP20
Pollution degree
maximum permissible according to DIN EN 61131-2:
Pollution Degree 2
Housing
Plastic housing for carrier rail mounting NS35/7,5 DIN EN 60715
Dimensions
width: 22.5 mm, length: 99 mm, constructional height: 114.5 mm
(dimensions without mating connectors)
Weight
145 g
Table 1: General technical data of the module