12
DIP
Modes and functions
Option
Effect
DIP1
OFF
DIP2
Advance warning
ON
the flashing light comes on and the operation begins after a 3
second warning
OFF
the flashing light comes on and the operation begins
immediately
DIP3
Opening mode
ON
step-by-step opening (the gate halts if a key command is
activated during opening, and closes if activated again)
OFF
collective opening (the control board does not obey the key
commands during opening)
DIP4
Automatic or step-by-step mode
(for pedestrian and total operation)
ON
automatic mode (the gate closes automatically after standby
time has passed, which is adjusted using T.E.). A key command
(or photocell activation) causes standby time to restart
OFF
step-by-step mode (the gate only closes when receiving the key
command)
DIP5
Automatic mode optional
(only if DIP4 = ON)
ON
during standby, the gate obeys the key commands (can be
closed before standby time finishes)
OFF
the gate cannot be closed until standby time finishes; a key
command will cause standby time to restart
DIP6
Gate movement
direction
ON
gate which opens to the left
OFF
gate which opens to the right
DIP7
Encoder
ON
encoder enabled
OFF
encoder disabled
DIP8
Slowdown
ON
the gate reduces its speed before reaching the stopper
OFF
the gate reaches the stopper at high speed
Function and mode selection using SW1 (DIP1 = OFF)
T.E (Standby Time): gate open standby time
If automatic functioning mode has been programmed
(DIP4=ON), set T.E. to adjust standby time with the gate
open (before automatic closing begins).
•
Minimum value: 0 seconds; maximum value: 90
seconds
P.M (Torque Regulator): motor torque
Use P.M. to adjust the maximum motor power value.
‹
Adjust the torque to respect the maximum closing
thrusts set out in Standard EN12453:2000. Make
the measurements as described in Standard EN
12445:2000.
W
aiting
Time
PO
T2
P268M
Potentiometer adjustment