background image

12

  

 

DIP

Modes and functions

Option

Effect

DIP1

OFF

DIP2

Advance warning

ON

the flashing light comes on and the operation begins after a 3
second warning

OFF

the flashing light comes on and the operation begins
immediately

DIP3

Opening mode

ON

step-by-step opening (the gate halts if a key command is
activated during opening, and closes if activated again)

OFF

collective opening (the control board does not obey the key
commands during opening)

DIP4

Automatic or step-by-step mode 
(for pedestrian and total operation)

ON

automatic mode (the gate closes automatically after standby
time has passed, which is adjusted using T.E.). A key command
(or photocell activation) causes standby time to restart

OFF

step-by-step mode (the gate only closes when receiving the key
command)

DIP5

Automatic mode optional 
(only if DIP4 = ON)

ON

during standby, the gate obeys the key commands (can be
closed before standby time finishes)

OFF

the gate cannot be closed until standby time finishes; a key
command will cause standby time to restart

DIP6

Gate movement 
direction

ON

gate which opens to the left

OFF

gate which opens to the right

DIP7

Encoder

ON

encoder enabled

OFF

encoder disabled

DIP8

Slowdown

ON

the gate reduces its speed before reaching the stopper

OFF

the gate reaches the stopper at high speed

Function and mode selection using SW1 (DIP1 = OFF)

T.E (Standby Time): gate open standby time

If automatic functioning mode has been programmed
(DIP4=ON), set T.E. to adjust standby time with the gate
open (before automatic closing begins).

Minimum value: 0 seconds; maximum value: 90
seconds

P.M (Torque Regulator): motor torque

Use P.M. to adjust the maximum motor power value. 

Adjust the torque to respect the maximum closing
thrusts set out in Standard EN12453:2000. Make
the measurements as described in Standard EN
12445:2000.

W

aiting

Time

PO
T2

P268M

Potentiometer adjustment