Gr.6
- Alarm 3 type - [r.F09]
This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Range: Proc = Alarm on process variable
bAnd = Band alarm on process variable
dEV
= Deviation alarm on process variable
ñAin = Alarm on Main control output value
SECn = Alarm on Secondary control output value
NOTE
: When alarm type has been changed the alarm threshold
will be forced to its default value and alarm status will be
cleared.
- Alarm 3 configuration - [r.F10]
This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Range: H.A.
= High alarm (outside band) with automatic reset
L.A.
= Low alarm (inside band) with automatic reset
H.A.Ac= High alarm (outside band) with automatic reset
and acknowledge
L.A.Ac= Low alarm (inside band) with automatic reset
and acknowledge
H.L.
= High alarm (outside band) with manual reset
L.L.
= Low alarm (inside band) with manual reset
NOTE
: When alarm configuration has been changed, the alarm
status will be cleared.
- Alarm 3 action - [r.F11]
This parameter is available only when OUT 3 is configured as
alarm 3 output (“O3.Fn” [C.E03] = “ALr.3”)
Range: dir
= direct action (Relay energized or SSr=1 in
alarm condition)
rEV
= Reverse action (Relay energized or SSr=1 in
non alarm condition)
Xkc-1-C0.P65
5/29/02, 11:59 AM
92
Содержание MKC
Страница 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Страница 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Страница 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Страница 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Страница 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Страница 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...