CnF. 2
40
- Valve position indication - [C.E06]
This parameter will be displayed only when open loop
servomotor control drive output is confi-gured.
Range: Fb
= The valve position is measured and displayed
no.Fb = The valve position is not measured
NOTE
: If the feedback option is not mounted, this parameter will
be forced to “no.Fb” (no feedback).
- OUT 5 function - [C.E07]
Range: nonE = Output not used
ñAin
= Main control output (linear)
SECn = Secondary control output (linear)
PV.rt = Process variable retransmission
SP.rt = Operative set point retransmission
NOTE
: When the option circuitry is not mounted the middle
display will show “no.Pr” (not present).
- OUT 5 range - [C.E08]
This parameter will be available only when Out 5 is configured
("O5.Fn" [C.E07] different from "nonE")
Range: 0-20
= 0
¸
20 mA
4-20
= 4
¸
20 mA
- OUT 5 retransmission initial scale value
- [C.E09]
This parameter will be available only when Out 5 function
[C.E07] is configured as “PV.rt” or “SP.rt”
Range: From -1999 to 9999
NOTE
: Decimal point is positioned as previously selected at
“CnF.1 - ñ.In.d” [C.d03])
- OUT 5 retransmission full scale value
- [C.E10]
This parameter will be available only when Out 5 function
[C.E07] is configured as “PV.rt” or “SP.rt”
Range: From -1999 to 9999
NOTE
: Decimal point is positioned as previously selected at
“CnF.1 - ñ.In.d” [C.d03])
Xkc-1-C0.P65
5/29/02, 11:59 AM
40
Содержание MKC
Страница 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Страница 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Страница 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Страница 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Страница 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Страница 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...