CnF. 1
36
- Auxiliary input type - [C.d10]
This parameter will be skipped when the auxiliary input option is
not mounted or "A.In.F" (auxiliary input function [C.d09]) is equal
to "nonE".
Range: 0-20
= 0
-
20 mA
4-20
= 4
-
20 mA
0- 5
= 0
-
5 V
1- 5
= 1
-
5 V
0-10
= 0
-
10 V
2-10
= 2
-
10 V
- Initial scale read-out of the auxiliary input
- [C.d11]
This parameter is available only when auxiliary input is
configured
Range: from -1999 to 9999
NOTE
: the decimal point will be automatically positioned as
selected for the main input.
- Full scale read-out of the auxiliary input
- [C.d12]
This parameter is available only when auxiliary input is
configured
Range: from -1999 to 9999
NOTE
: the decimal point will be automatically positioned as
selected for the main input.
- Filter on auxiliary input - [C.d13]
This parameter is available only when auxiliary input is
configured
Ranges: from 0 (no filter) to 8 seconds.
NOTE
: this is a first order digital filter applied to the measured
value made by the auxiliary input.
- Auxiliary input activation mode - [C.d14]
This parameter is available only when auxiliary input is
configured
Range: norñ = The auxiliary input activation is controlled by
external contact, front key or serial link
Xkc-1-C0.P65
5/29/02, 11:59 AM
36
Содержание MKC
Страница 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Страница 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Страница 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Страница 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Страница 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Страница 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...