Gr.3
79
- Alarm 3 threshold - [r.C08]
This parameter is available when alarm 3 is configured as
process, deviation, main power output or secondary power
output alarm (“A3.tP” [rF.09] = “Proc” or “dEV” or “ñAin” or
“SECn”)
Range: - in engineering units within the span limits for process
alarm;
- from -1000 to 1000 digits for deviation alarm;
- from 0.0% to 100.0 % for control output alarms.
NOTE
: The span limits are configured by “ñ.In.L” [C.d05] and
“ñ.In.H” [C.d06].
- Low threshold used when the alarm 3 is a
band alarm - [r.C09]
This parameter is available only when the alarm 3 is configured
as band alarm (“A3.tP” [rF.09] = “bAnd”)
Range: from 0 to -1000 digits.
- high threshold used when the alarm 3 is a
band alarm - [r.C10]
This parameter is available only when the alarm 3 is configured
as band alarm (“A3.tP” [rF.09] = “bAnd”)
Range: from 0 to 1000 digits.
NOTE
: The "bA3.L" and "bA3.h" values are algebraically added
to the operative set point in order to obtain the band limits.
- Alarm 4 threshold - [r.C11]
This parameter is available when alarm 4 is configured as
process, deviation, main power output or secondary power
output alarm (“A4.tP” [rF.13] = “Proc” or “dEV” or “ñAin” or
“SECn”)
Range: - in engineering units within the span limits for process
alarm;
- from -1000 to 1000 digits for deviation alarm;
- from 0.0% to 100.0 % for control output alarms.
NOTE
: The span limits are configured by “ñ.In.L” [C.d05] and
“ñ.In.H” [C.d06].
Xkc-1-C0.P65
5/29/02, 11:59 AM
79
Содержание MKC
Страница 1: ...r USER MANUAL PKC MKC 170 IU0 XKC 0C1 05 02 Xkc 01 C0 P65 5 29 02 11 58 AM 1...
Страница 2: ...Xkc 01 C0 P65 5 29 02 11 58 AM 2...
Страница 4: ...Xkc 01 C0 P65 5 29 02 11 58 AM 4...
Страница 7: ...3 Fig 2 B OUTLINE AND CUT OUT DIMENSIONS FOR MKC MODEL Xkc 1 C0 P65 5 29 02 11 59 AM 3...
Страница 132: ...A 11 Xkc AA0 p65 5 29 02 12 00 PM 11...
Страница 140: ...Xkc Z C0 p65 5 29 02 12 01 PM 1...