Appendix A Specifications
Appendix A-2
TESLA LITE User Manual
D03283R01.10
Recording and Logging
Transient Fault
Record length 10 seconds
0 to 1 sec pre-trigger time
Dynamic Swing
Record length900 seconds to 15 minutes
1 sample per cycle,
0 to 60 secs pre-trigger time
Event Logging
250 Events in the regular log, up to 1000 events per day
in long trend log
Long term event logging is part of the
trending function.
Record Storage
Up to 150 records
Trending
Available trend channels
Any of the recorder’s existing configured analog chan-
nels (input or calculated) can be trended.
Evaluated phasor magnitude and angle
quantities will be recorded as separate
channels.
Accumulation mode
Minimum, maximum, average, damped or undamped.
Sample Interval
User selectable sample interval from 10 seconds to 1
hour in 1 second increments.
All channels produce trend data simulta-
neously at the selected rate.
Maximum number of
channels
Up to 45 channels can be trended simultaneously.
A channel with multiple accumulation
modes is treated as multiple channels
(e.g. the trending of minimum, maximum
and average readings of a selected input
would require 3 trend channels).
Trend storage
The recorder can store 15 days of data from each trend
channel, regardless of the number of configured trend
channels.
This is a non-configurable parameter.
Channels and Triggers
Analog Inputs
High and low threshold, positive and negative rate of
change, harmonic level, THD level, sags, swells
All triggers have independent controls for
delay, logging, transient or swing record
initiation, alarm contact activation and
cross triggering.
Summations
High/low threshold, +/- rate of change
2 or 3 input channels
Positive Sequence
High/low threshold, +/- rate of change
Negative Sequence
High level
Zero Sequence
High level
Watts/Vars
High/low threshold, +/- rate of change
Frequency
High/low threshold, +/- rate of change
Impedance
Positive sequence circle
External Inputs (digital)
Rising edge, falling edge or both
Logic
Rising edge, falling edge or both
Fault Locator
Triggered by internal or external events
Sags and Swells
Sag and swell detection can be enabled on any analog
input channel configured as a voltage.
Interface & Communication
TESLA LITE Power System Recorder
Содержание tesla lite
Страница 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 20: ......
Страница 24: ......
Страница 78: ......
Страница 126: ......
Страница 134: ......
Страница 214: ......
Страница 234: ......
Страница 280: ......
Страница 282: ...Appendix G TESLA LITE Drawings Appendix G 2 TESLA LITE User Manual D03283R01 10 Figure H 1 Mechanical Drawings 401 450 ...
Страница 284: ......
Страница 288: ......