8 Configuring the Recorder
D03283R01.10
TESLA LITE User Manual
8-23
Scale Factor
Specifies a multiplier for each of the inputs. The scale factor is applied
in the secondary domain.
Angle Offset
Specifies a phase angle shift to be applied to each of the inputs.
Note that when an offset is specified, a high speed summation record-
ing - which uses sample by sample addition rather than phasor addi-
tion - is not generated. All other functions, including low speed
recording, are available and will reflect the offset.
Trigger Settings
Rate of Change
Interval
Specifies the period of time over which both positive and negative rate
of change is measured. 0.5 to 8.0 cycles.
Limit
Specifies the trigger levels for the magnitude triggers and the magni-
tude portion of the rate for the rate of change triggers. The period por-
tion of the rate is specified by the
Rate of Change Interval
.
Delay
Specifies how long the trigger condition must be present before a trig-
ger is declared. 0 to 1,200 seconds in half-cycle increments.
Trigger Actions
Enable
Enables or disables the associated trigger. A trigger can be disabled
without altering the rest of its settings.
Fault
Initiates a fault (high speed) recording when triggered.
Swing
Initiates a swing (low speed) recording when triggered.
If both Fault and Swing are enabled, the recorder will attempt to cre-
ate a combined record.
Log
Logs a message in the Event Log when triggered.
Notify
Contacts the RecordBase Central Station when triggered. Can be
used to initiate wide area swing recordings and/or automated record
transfer (“Notify” on page 7-13)
Cross Trigger
Activates the cross-trigger contact (#6) to trigger another device.
Priority
Specifies the priority to be assigned to records created by this trigger.
The priority is used to determine Central Station notification.
1 - 3 (3 is the highest priority). (“Notify” on page 7-13).
Alarm Contact
Specifies a rear panel contact to be closed when triggered. Contacts
are closed momentarily for one second. Contact assignment is not
exclusive, allowing multiple triggers to activate the same contact.
Contacts assigned for storage alarms (“TESLA Alarms” on page 8-6)
will not be available for use here.
Table 8.10: Summation Channel Settings
Содержание tesla lite
Страница 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 20: ......
Страница 24: ......
Страница 78: ......
Страница 126: ......
Страница 134: ......
Страница 214: ......
Страница 234: ......
Страница 280: ......
Страница 282: ...Appendix G TESLA LITE Drawings Appendix G 2 TESLA LITE User Manual D03283R01 10 Figure H 1 Mechanical Drawings 401 450 ...
Страница 284: ......
Страница 288: ......