6.
Parameter Adjustment Procedure
1. Amplitude adjustment
Press the programming Mode key (P)
Observe a “C 000” in the display
Using Cursor keys select “C 002”
Press P key, observe “A 000”
Now an amplitude setting in percent can be entered
Press P key to return controller to normal operation
2. Other feeder values
Press P key, using cursor key move to “C 096.”
Press P key to select required parameter
“A 000” = Amplitude (Feeder) [%]
“P 000” = Maximum control limit [%],
adjustable 20…100%
“
Ґ
000” = Soft start time
“L 000” = Soft stop time [sec.], operates when unit
switched off by track sensor
Press P key to return to programming mode
3. Set source and output waveform
Press P key, using cursor key move to “C 003”
Press P key to select required parameter
“E.S.P.” = external set point, 0 for keys,
1 for external
If 1 is selected, control will operate with
potentiometer. If remote potentiometer is used
SET Amplitude “A” to 0%. Bias upward by raising
amplitude level.
If 1 is selected, press P key and select “4..20 0”
Select 1 for set point values 0…10 v, dc or 0…20mA
Select 0 for set point values 4.…20mA DC
Press P key to select “SP.2 0” for track control mode
and “SP.2 1” for dual set point operation
Output waveform is factory set and should
not be adjusted
Please consult Eriez for more information
concerning Track Control.
Installation
(cont.)
4. Return to saved settings
Press P key, using cursor key move to “C 210”
Press P key to select required parameter
“FAC” = factory settings, using cursor key select
“SAFE” (loads factory settings)
Press P key to observe “USPA”, using cursor key
select “SAFE” (return to user parameters)
Press P key to return to normal operating model
5. Storing user parameters
Press P key, using cursor key move to “C 14.3”
Press P key to select required parameter
“PUSH” = save parameters, using cursor key select
“SAFE” (parameters are saved)
Press P key to return to normal operating model
6. When an "OFF" is displayed and will not clear
Go to code "003" and select EN=1
If control is wired for remote, the remote switch
should be closed or a jumper placed between term's
5 and 6. (user enable).