EG_GenPro25e_1055_UG_002_UK
Page 35 / 58
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCOGENER reserves the right to make any modification.
Dct_427_02
3.8 BOOT
This signal must NOT be connected, NOT used. The use of the BOOT function is strictly
reserved for the manufacturer and distributors.
Table 29 : Description BOOT input
Signal
Connector 16 pins
Pins number
I/O
Kind of I/O
Description
BOOT
GND
3
9
I
SCHMITT
Boot modem
Table 30 : Conditions of use of BOOT signal
Parameters
Conditions
Min.
Typ.
Max.
Unit
V
IL
Input Voltage
– Low
-0.3
0.8
V
DC
V
IH
Input Voltage
– High
2
3.3
V
DC
RIPU
Internal Pull-Up Resistor
5.38K
Ω
Figure 18 : Internal electrical scheme of BOOT
The use of the BOOT signal must be done through a transistor assembly or via dry contact.
The integrator has the responsibility to protect the input from electrical perturbations and to
respect the functioning parameters values.