SERVICE MANUAL TANGO KW (short version) ENGLISH
Autori: Serralunga M.
16/07/2020
23
NO COPYING IN ANY FORM WITHOUT WRITTEN PERMISSION FROM EPTA QUALITY MANAGEMENT
Disconnect the vacuum machine from the low pressure pipe (
A
); connect the gas bottle
(
8
) to the circuit.
Switch on the refrigerator, in order to insert the refrigerant gas into the circuit.
WARNING! in order to avoid damages on the thermodynamic system or danger for
technical assistant; be sure to have connected the gas bottle to the refrigerator circuit.
The refrigerator must be ON for 5-6 minutes, then disconnect the refrigerator from current.
Take the plier (
3
) and pinch the low pressure pipe (
A
), then remove refrigerant junction.
Put a drop of Lokprep sealant (
4
) on the low pressure pipe (
A
).
R
2
9
0
3
A
Picture example
of compressor