11
CAUTION
The controller may be damaged if a common-positive controller is used and the
positive electrode is grounded in the common-negative system.
Step 4
:
Connect
accessories
Connect the remote temperature sensor cable
(
Model:RT-MF58R47K3.81A
)
(
Model:RTS300R47K3.81A
)
Connect the remote temperature sensor cable to the interface
①
and place the other end close to
the battery.
CAUTION
Suppose the remote temperature sensor is not connected to the controller. In
that case, the default battery charging or discharging temperature setting is
25 °C without temperature compensation.
Connect the accessories for RS485 communication
Refer to chaper4
“Control Parameters Setting.”
Step 5
:
Powered on the controller
Connect the battery fuse to power the controller. Then check the battery indicator's status (the
controller operates normally when the indicator is lit in green). Connect the fuse and circuit breaker
of the load and PV array. Then the system will be operating in preprogrammed mode.
CAUTION
If the controller is not operating properly or the battery indicator on the controller
shows an abnormality, please refer to 5.2 “Troubleshooting.”
Temperature Sensor
Remote Temperature Sensor
Cable (Optional)