16
Output voltage
Set to ON
Output 24V
CPM/LPM
Load working
Modes
(only valid for load
2)
Set to OFF
CPM(Charging Prior Mode)
(Default)
Set to ON
LPM(Load prior mode
①
)
①
The load prior mode will be enabled when the battery voltage reaches the low voltage
disconnect voltage and the PV array charging current reaches more than 7A for 10
minutes.
WARNING
Before connecting loads, ensure the voltage level of the load is
equal to the output voltage level corresponding to the DIP switch.
The load may be damaged if the output voltage level is higher than
the load voltage.
2.6
Load operation mode
Load
Working
modes
Definition
Load 1
Manual
mode(Default
load ON)
The load output will be turned off when the battery
voltage reaches the Under Voltage Warning Voltage
(UVW).
The load output will resume when the battery voltage
reaches the Under Voltage Warning Reconnect
Voltage (UVR).
Load 2
Manual
mode(Default
load ON)
Set enable switch to CPM(default)
The load output will be turned off when the battery
voltage reaches the Low Voltage Disconnect Voltage
(LVD).
The load output will resume when the battery voltage
reaches the Low Voltage Reconnect Voltage (LVR).
Set the enable switch to LPM
①
Mode 1: The load output will discontinue when the
battery voltage reaches the Low Voltage Disconnect
Voltage and the PV array's charging current reaches
more than 7A for 10 minutes. It will be turned on for