6
P
lease note that the following
measurements are based on values
provided by the unit quality assurance by
the European Standard EN 60335-53-2. In
principle, you must mount the oven sensor
where temperatures are the highest. Illust.
7 gives you an overview of the mounting
point of the sensor.
Warning: When connecting the vaporizer
make sure it is correctly attached to the
water bath (WB) and low water shutoff
(WM). If you switch these connections, you
disable the water deficiency function and
bypass the thermostat. As a result, the
vaporizer will overheat.
This is a fire hazard!!
I
llust. 6 shows the circuit diagram. The
control unit can detect water deficit if there
is a zero-potential feed at the WM-input.
Illust. 6
2.2.3 Connecting the sauna lamp
The sauna lamp must be splashproof (by
Standard IP54) and suitable for
temperatures up to 140°C. The sauna
lamp can be mounted anywhere except in
the area of the rising hot air above the oven.
2.3 Connecting the sensor lines
You should not install sensor and power
supply lines together, or lead them through
the same conduit. This can lead to
interferences in the electronics, such as
"fluttering" in the switch protectors. If it is
absolutely necessary to install them
together, or the wire is longer than 3m, you
should use a shielded sensor line such as
the LIYLY-O (4 x 05, mm²). Connect the
shielding to mass in the control unit.
Illust. 9
Illust. 8
20 cm
Illust. 7
Mounting the oven sensor
1. Mount the oven sensor in cabins up to
2 x 2m according to Illust. 7 and 8, in larger
cabins according to Illust.s 7 and 9.
connectors in the control
unit
vaporizer
TL
black
brown
blue
green/yellow
WQ = water quench
WS = water shortage
TL = temperature limiter
N
35 cm
19 cm
3 kW
WQ
WS
english