X2
F2
F1
L1 L2 L3
N
W
V
U
N
N L
LSG
V1
S1
N
Example of the error message
for overheating limiter fuse (DE)
Hole
Sauna ceiling
Jumper for heating time
limitation setting:
6 h, 12 h, unlimited
centre sensor housing in
the middle of the plank
Second temperature
sensor (optional)
sensor cables
Fig. 11
Fig. 12
6. After completed installation and correct
commissioning of the control unit, the line
for overtemperature protection must be
checked for short-circuits. In order to do this,
disconnect one of the white cables in the
sensor casing. The respective error message
shall appear in the display.
12:00
Sensor -
break
Attention!
Make sure not to confuse the
sensor cables at X2 connector! This may cause
the F2 fuse to burn, for replacement see page
„replace device fuse“
Bankfühler
2nd temper. sensor
Temperaturfühler
Temperature sensor
142°C
KT
Y
11
/5
X2
weiß/white
rot/red
11
GB