Initial Installation

QUALIFIED INSTALLERS ONLY

g

as

 L

ine

 c

onnection

 

anD

 t

esting

:

WARNING:

 Only persons licensed to work with gas piping may make the necessary gas connections to 

this appliance.  

Figure 50: Fully Labeled Gas Valve.

GAS LINE CONNECTION

• 

This stove is equipped with a certified flexible pipe 

located on the right side of the unit terminating in a ⅜” 

male NPT fitting. Consult your local authorities codes or 

the CAN/CGA B 149 (1 or 2) installation code in Canada, 

or in the USA gas installations follow either local codes 

or the current edition of the National Fuel Gas Code ANSI 

Z223.1.

• 

The  efficiency  rating  of  this  appliance  is  a  product 

thermal  efficiency  rating  determined  under  continuous 

operating conditions and was determined independently 

of any installed system.
The appliance and its shutoff valves must be disconnected from the gas supply piping system during any 

pressure testing where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff 

valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 

½ psig (3.45 KPa).

Always  check  for  gas  leaks  with  a  soap  and  water  solution  after  completing  the 

required pressure test.

TO TEST VALVE PRESSURES

The pressure taps are located on the left side of the valve 

• Turn set screw 1 turn counter clockwise to loosen, 

• Place 

5

/

16

” (8 mm) I.D. hose over pressure tap system. 

• Check pressures using a manometer.

• When finished, release pressure, remove hose & tighten set screw.

Table 7: Pressure and BTU Information.

Natural Gas

Propane

Main Burner

#39 DMS

#53 DMS

Manifold Pressure

3.8” W.C. / 0.95KPa

11.0” W.C. / 2.7KPa

Min. Manifold Pressure

1.1” W.C. / 0.27KPa

2.7” W.C. / 0.67KPa

Max Supply Pressure

7.0” W.C. / 1.74KPa

13.0” W.C. / 3.28KPa

Min. Supply Pressure

5” W.C. / 1.24KPa

12.0” W.C. / 2.98KPa

Max BTU/hr Input

30,000 BTU/hr (8.80KW)

26,500 BTU/hr (7.76KW)

Min. BTU/hr Input

17,000 BTU/hr (4.98 KW)

14,000 BTU/hr (4.10KW)

Venturi Setting

1

/

16

” min.

3

/

16

” min.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Pilot Adjustment 

Screw

Manifold

Pressure Tap

Inlet

Pressure Tap

Servo

Regulator

Содержание Westport IPI Steel

Страница 1: ...operty damage personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier Version Fran aise www enviro com fr html W A R R A...

Страница 2: ...your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualifi...

Страница 3: ...ed by a qualified installer service agency or gas supplier This installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the Nat...

Страница 4: ...tive Surfaces 16 Safety Screen 16 Glass Door Removal 16 Burner Removal 16 Access Panels 17 Fuel Conversion 17 Fuel Conversion 18 Initial Installation 19 Introduction 19 Unit Install Preperation 20 Pla...

Страница 5: ...NSI Z21 88 2014 CSA 2 33 2014 VENTED GAS FIREPLACE HEATERS CAN CGA 2 17 M91 R2014 GAS FIRED APPLIANCES FOR HIGH ALTITUDES CSA P 4 1 02 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY This ENV...

Страница 6: ...an result in carbon monoxide CO poisoning and possible death Dimensions 26 1 4 66 5 19 1 2 49 7 271 2 70cm 241 8 61 3cm 191 8 48 4cm 16 40 7cm Figure 1 Westport Exterior Dimensions Rating Label Locati...

Страница 7: ...nd to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Read the owner s manual incl...

Страница 8: ...ight If the flames look like this no venturi adjustment is needed If the flames are fairly short and mostly blue the fireplace is getting too much air Therefore the air shutter should be closed slight...

Страница 9: ...t will start to smoke which can irritate some people After the unit has gone through the first burn turn the unit OFF including the pilot and let the unit completely cool Then remove the glass and cle...

Страница 10: ...index through Thermostat functions Figure 5 6 Figure 5 Proflame 2 Transmitter System Description The Proflame 2 Remote Control System consists of two 2 elements 1 Proflame 2 Transmitter 2 Integrated F...

Страница 11: ...dance with the particular Proflame 2 system configuration The IFC has a red reset button at the front right corner that is used is to synchronize the Transmitter when using the for the first time or a...

Страница 12: ...see Figure 7 Turn on the Appliance Press the ON OFF Key on the Transmitter The Transmitter display will show all active Icons on the screen A single beep from the IFC will confirm reception of the co...

Страница 13: ...Key Figure 4 until the word SMART appears to the right of the temperature bulb graphic Figure 11 To adjust the set temperature press the Up or Down Arrow Keys until the desired set temperature is disp...

Страница 14: ...ies used the number of ignitions of the appliance the number of changes to the room thermostat set point etc When the IFC batteries are low No beep will be emitted when it receives an On Off command f...

Страница 15: ...ny dust off the logs and remove any lint from the burner and pilot At this time inspect the burner pan for cracking or severe warping If a problem is suspected contact the dealer Check the logs for de...

Страница 16: ...ght up and out see Figure 6 and 7 To remove the door fascia lift up and then away from the stove figure 7 Ensure the door is properly fastened after cleaning before attempting to re light the applianc...

Страница 17: ...l parts supplied with this conversion kit If any parts have been damaged or are missing contact your dealer distributor or courier company to have them replaced before starting this installation Conve...

Страница 18: ...onfirm the inlet and manifold pressures are within the acceptable ranges as directed in section Intial Intallation Gas Line Connection and Testing an approved pipe thread sealant or approved Teflon ta...

Страница 19: ...he four steel legs using the supplied hardware and a 3 8 wrench or socket see Figure 15 Stand the stove up Locate a position where the flue system of the stove can be properly installed without damagi...

Страница 20: ...mum allowable wall thickness is 10 inches 25 4 cm 1 inches 3 8 cm clearance to combustibles must be maintained Select the amount of vertical rise desired for vertical to horizontal type installations...

Страница 21: ...must be within the shaded area of Figure 23 If a 90 elbow is used in the horizontal plane 36 91 4 cm must be subtracted from the allowable horizontal run There are three 3 basic types of Direct Vent...

Страница 22: ...12 in 30 cm Clearance from permanently closed window to prevent condensation D 24 in 60 cm Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft 60 c...

Страница 23: ...cone 1 5 190 cm length of 4 10 cm double walled flex pipe 12 9 16 tech screws 1 5 190 cm length of 6 16 8 cm double walled flex pipe 8 1 wood screws Please ensure that all components are supplied with...

Страница 24: ...6 16 25 cm flex intake liner over the collar secure the flex liner with three 3 sheet metal screws evenly spaced 14 Attach the vent terminal to the outside of the house using four 4 wood screws provi...

Страница 25: ...0B 90 elbow black 950 4DT VS SV4VS Vinyl siding standoff sheild 942 4DT WT SV4RSN 4DWT Wall thimble 953 4DT SC SV4FC 4DSC Storm collar 963 4DT FS SV4BF 4DFSP Fire stop 988 4DT WS B SV4BM 4DWS Wall str...

Страница 26: ...is preferable to using 90 elbows Also a shorter vent system will perform better than a longer one Initial Installation QUALIFIED INSTALLERS ONLY V e n t R e s t r i c t o r P o s i t i o n s If top ve...

Страница 27: ...will not be visible from the outside on black pipe They may be located by examining the inside of the female ends as shown in Figure 25 Notes a Twist lock procedure four 4 indentations located on the...

Страница 28: ...le will conceal it see left image in Figure 27 7 Slide the decorative wall thimble up to the wall surface and attach with the screws provided Apply decorative brass or chrome trim if desired see right...

Страница 29: ...p an elbow strap over the exposed sections bend the support straps outwards and push the elbow strap down to the roof level as shown in Figure 31 Tighten the clamp around the pipe section Use a level...

Страница 30: ...12 to 9 12 2 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 1 22 Over 12 12 to 14 12 5 1 52 Over 14 12 to 16 12 6 1 83 Over 16 12 to 18 12 7 2 13 Over 18 12 to 2...

Страница 31: ...e centerline of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point From the roof locate the drill hole and mark the outline of the Cathedral Ceiling Su...

Страница 32: ...7 and Initial Installation Vent Configurations and Restrictor Settings For other corner installations refer to Figure 38 and Initial Installation Vent Configurations and Restrictor Settings 5 Using ti...

Страница 33: ...nce 1 Carefully remove the stovetop and place on a soft surface as not to damage the painted finish see Figure 39 2 Remove the four 4 screws that hold the flue collar elbow to the unit body see Figure...

Страница 34: ...sition Attach a small section of pipe on the unit and mark exterior wall where vent would pass through the wall Cut a 10 25 4 cm minimum hole in the wall to maintain clearances to combustibles Frame h...

Страница 35: ...l the vent section through the wall and then install the vent termination Seal around the termination using a non hardening mastic CORNER INSTALLATION This type of installation can be used in a corner...

Страница 36: ...sure that the wires are not pinched between the adaptor and the collar and or flue outlet Ensure that the opening of the Drafthood Adaptor is not blocked or obstructed 3 Being careful not to run any w...

Страница 37: ...tructed chimney vent system see Figure 46 47 In either case the fireplace may be connected to the chimney vent using a 4 10 cm single wall vent connector When an existing masonry chimney is utilized f...

Страница 38: ...ove the four mounting screws holding the spill switch bracket and remove the bracket see Figure 49 4 Remove and replace the spill switch with a 50 885 Spill Switch Assembly using a T 20 torx type driv...

Страница 39: ...he appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or...

Страница 40: ...ectly into a properly grounded three prong outlet DO NOT cut or remove the grounding prong from this plug CAUTION When servicing controls label all wires prior to disconnection Wiring errors can cause...

Страница 41: ...tlet and turn the unit on to ensure fan operation Installation of Log Set and Embers The placement of the logs is not arbitrary If they are positioned incorrectly the flames can be pinched and will no...

Страница 42: ...oss the burner tray Do not allow any embers to rest against pilot assembly See diagram provided for proper ember placement DO NOT pack this ember material as this could create an unsafe condition leav...

Страница 43: ...ring process It is advisable to open a window or door as the unit will start to smoke and can irritate some people After the unit has gone through the first burn turn the unit off including the pilot...

Страница 44: ...line up the slots on the bracket with the holes at the top of the baffle Use two 2 of the provided screws to hold the bracket in place Ensure the top panel is centered before tightening the four 4 sc...

Страница 45: ...s below Safety Screen Removal 1 Turn off the stove and allow it to fully cool down 2 Remove the fascia as outlined in the Glass Door and Fascia Removal section of the manual 3 Lay the fascia face down...

Страница 46: ...ew check pilot head for damage Check thermocouple voltage at valve It must be greater than 5 mV If low replace thermocouple Air in gas line pilot dies while knob is depressed Bleed line Check gas line...

Страница 47: ...t Only EGWP 087 Releif Door with Gasket 50 3369 Shoulder Bolt Hardened Bushing Nut Set of 2 EF 124 7 Pan Burner Only 30 055 8 PSE Pilot Assembly Intermittant Pilot 50 3026 Pilot Gasket EC 021 9 Profla...

Страница 48: ...ef EC 044 Battery Holder 4 x AA 50 3027 Embers 50 491 4 Flex Coupler 50 497 Westport Replacement Safety Screen 50 3060 Owner s Manual 50 3403 Brick Panel Set 50 1038 Log Set With Embers Complete 50 10...

Страница 49: ...49 Parts Diagram Components 16 17 1 2 3 15 14 13 11 10 8 7 4 5 6 12 9 DATE 11 04 2017 BY SHERWOOD INDUSTRIES LTD INTERNAL ASSEMBLY MANUAL SHEET STOVE UPDATED BY REVISION...

Страница 50: ...Notes 50...

Страница 51: ...er including serial number This warranty does not cover any discoloration of the safety screen mesh Exclusions An expanded list of exclusions is available at www enviro com help warranty html This war...

Страница 52: ...______________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy...

Отзывы: