background image

Install 2 spring spacers around the flex pipe. Slide the horizontal section of pipe 
over the flexible liner and install through the wall thimble. Ensure that this 
portion of pipe slides onto the vent termination cap. Slide the inside finished 
collar over the horizontal section of pipe and secure to wall using the screws 
provided. Slide the 90° elbow over the flex pipe. Stretch the flex liner to a 
length long enough to ensure the flex liner can be easily connected to the flue 
outlet of the appliance. Install the remaining spring spacers over the flexible 
liner and install the vertical section of pipe (DO NOT SLIP THESE SECTIONS 
OF PIPE TOGETHER, YOU WILL REQUIRE SOME MOVEMENT IN THESE 
PIPE SECTIONS IN ORDER TO SECURE THE FLEX PIPE TO THE FLUE 
OUTLET ON THE APPLIANCE.) 

 

12

 
Place a bead of high temperature silicone on the flue pipe and slide flex liner 
over collar, secure the flex liner with 3 sheet metal screws evenly spaced. 
 
Align all straight sections of pipe, slipping all joints together and installing 3 
sheet metal screws evenly spaced. 
 
A small can of touch up paint has been supplied with this kit. Lightly touch up 
any scratches that might have accord during the installation process. 
 
Install brass decorative rings around each joint making sure this decorative ring 
covers the sheet metal screws which secure each section of pipe together and 
secure to vent pipe in the slotted tab on the backside of the pipe so that the 
fastener would not be easily seen. 
 
Secure the horizontal section of pipe to the inside finished collar by installing a 
screw in the tab on the inside finished collar. (THIS WILL PREVENT THE PIPE FROM BEING DISCONNECTED AT THE 
VENT TERMINAL.) 

SPRING 

SPACERS

 
Light the appliance and ensure proper operation. 
 
 
 

WALL 

FRAMING 

HORIZONTAL WALL 

TERMINATION 

WALL THIMBLE

FIRE STOP 

DECORATIVE 

BRASS RINGS 

INSIDE 

FINISHED 

COLLAR 

EXHAUST

4” FLEX 

PIPE 

COMBUSTION 

AIR 

6 5/8” OUTER 

PIPE 

Содержание EG-40

Страница 1: ...on may result causing property damage personal injury or loss of life installation and service must be performed by a qualified installer service agency or the gas supplier Do not store or use gasolin...

Страница 2: ...tallation must conform to local codes or in the absence of local codes with the current CAN1 B 149 installation code in Canada or the current National Fuel Gas Code ANSI Z223 1 in the USA To prevent i...

Страница 3: ...IGH ALTITUDE SPECS ENVIRO EG 40 DIRECT VENT UNITS Have all been certified for use with either natural or propane gases See control panel and rating label Are not for use with solid fuels Must not be c...

Страница 4: ...aintenance Locate a position where the flue system of the stove can be properly installed without damaging the integrity of the building E g cutting a wall or ceiling joist The stove can be installed...

Страница 5: ...inimum K Clearance to a mechanical air supply inlet 6 feet 1 8m minimum L Clearance above paved side walk or paved driveway located on public property 7 feet 2 1m minimum M Clearance under verandah po...

Страница 6: ...PERMITTED TO REACH THE OUTSIDE VENT TERMINATION BEFORE BEGINNING THE INSTALLATION TAKE CARE TO ENSURE AN APPROPRIATE OUTSIDE LOCATION FOR THE VENT TERMINATION CAN BE ACCOMMODATED FOLLOW THE VENT LENG...

Страница 7: ...dentations located on the female end of the pipes and fittings are designed to slide straight onto the male ends of adjacent pipes and fittings by orienting the four pipe indentations so they match an...

Страница 8: ...nts excessive heat from possibly melting the vinyl siding material Note that the horizontal vent termination bolts onto the flat portion of the vinyl siding standoff Shaded area in FIG 12 so that an a...

Страница 9: ...pipe and elbows may be utilized in the attic as well as above the roofline The galvanized finish is desirable above the roofline due to the higher corrosion resistance STEP 6 Once the pipe sections h...

Страница 10: ...t the second floor and any subsequent floors FIG 19 The opening should be framed to 10 inch x 10 inch inside dimensions in the same manner as shown in FIG 16 2 Any occupied areas above the first floor...

Страница 11: ...ide on a location for the unit that will meet any or all local code requirements Refer to sections in this manual Deciding Were To Locate Your Stove and Planning Your Installation Set the appliance in...

Страница 12: ...liner over collar secure the flex liner with 3 sheet metal screws evenly spaced Align all straight sections of pipe slipping all joints together and installing 3 sheet metal screws evenly spaced A sm...

Страница 13: ...nimum 4 flex liner to the top of the CLASS A chimney Placing a bead of high temperature silicone to the Simpson Cap adapter and securely attach the flex liner to the adapter Secure the cap adapter to...

Страница 14: ...t is very important to install these logs in their correct position to insure safe optimum operating conditions Open the door of the fireplace Place the logs on the log supports Close the door and tig...

Страница 15: ...f all electrical power to the appliance 3 Turn the gas control knob clockwise to the off position 4 Open door Wait five 5 minutes to clear out any gas Close door If you smell gas including near the fl...

Страница 16: ...first 4 hours of use See page 14 After that depending upon the amount of use cleaning should be required no more than two or three times per season To clean the door use a mild glass cleaner and a so...

Страница 17: ...d Bleed line Check gas line pressure Contact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pressure Check for flame impingement on thermopile if low see Pilot will...

Страница 18: ...the current edition of the National Fuel Gas Code ANSI Z223 1 UPON CONNECTION MARK APPROPRIATE FUEL TYPE ON WARNOCK HERSEY RATING LABEL LOCATED ON THE INSIDE OF THE RIGHT HAND SIDE PANEL Manifold Pres...

Страница 19: ...ly to the floor WARNING ELECTRICAL GROUNDING INSTRUCTIONS This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged into a properly gr...

Страница 20: ...Voltage Thermostat REMOVING THE BLOWER 20 1 Turn the unit off and remove the log set 2 Remove the burner tray assembly by removing the screw on either side of the tray between the front and rear burne...

Страница 21: ...lot orifice First remove the two 2 T 20 Torx screws that hold the pilot assembly to the burner tray Lift the pilot assembly from the burner tray Using a 10mm wrench disconnect the pilot line from the...

Страница 22: ...ts only thereafter The paint on the Metal Brick Liner may peel This is due to the extreme conditions applied to the paint and is no way covered under warranty Your dealer shall make all claims under t...

Страница 23: ...g Harness Complete 2 pieces 30 014 Freestanding Burner Control NG Complete EC 040 Freestanding Fan Control Knob 30 015 Freestanding Burner Control LP Complete EC 043 IEC Power Cord 30 017 Rear Burner...

Страница 24: ...r 2003 EG40 GAS TRAY AND DOOR ASSEMBLIES Rear Venturi EG40 099 S I T Nova 820 Valve EC 006 NG EC 007 LPG S I T Piezo Ignitor EC 023 Burner Switch EC 025 Light Switch EC 066 FS Fan Controller EF 045 FS...

Страница 25: ...ing Side Panel Cabinet EG40 086 Flue Pipe Freestanding Pedestal Wiring Plate Freestanding Pedestal Box Cover EG40 307 1x1 Side Cabinet Hinge EC 054 Freestanding Side Panel Cabinet EG40 086 Convection...

Страница 26: ..._________ Name of Installer ___________________________________________ Address _______________________________________ ___________________________________________ ____________________________________...

Отзывы: