Initial Installation
WARNING: Operation of this heater when not connected to a properly installed and maintained
venting system can result in carbon monoxide (CO) poisoning and possible death.
c
LeaRances
to
c
ombustibLes
:
Figure 24: Mantle width and height.
Maintain sufficient clearances for operation, service and
maintenance.
• A minimum distance of 23
1
/
2
” (597 mm) is required
from the centerline of the unit to the sidewalls.
• Minimum clearance for any combustible facing is 40”
(1016 mm) from the bottom of the unit.
• A 8” (203 mm) wide mantel can be mounted at a
minimum height of 40” (1016 mm) from the bottom of
unit.
• If installed with a minimum of
1
/
2
” (13 mm) raised
hearth, there must be a minimum of 16” (406 mm) of
non-combustible material in front of the unit.
• If installed where the hearth is flush with the
combustible flooring, there must be a minimum of 18”
(457 mm) of non-combustible material in front of the
unit.
• Minimum ceiling clearance is 60” (1524 mm) from
bottom of unit.
m
inimum
f
iRepLace
s
ize
:
Table 3: Minimum dimensions of fireplace for E44 to be installed into.
Width At Front
Width At Back
Height
Depth
Fireplace Dimensions
34” (864 mm)
24” (610 mm)
24” (610 mm)
18
1
/
2
” (470 mm)
NOTE: Space must be provided for gas line on right side of unit for servicing purposes.
40"
(1016 mm)
minimum
from bottom
of unit
8" (203mm) Mantel
40"
(1016 mm)
minimum
from bottom
of unit
Combustible
Facing
non-combustible
hearth
16"
(406 mm)
minimum
from wall
If hearth is raised
a minimum of 1/2”
18"
(457 mm)
minimum
from wall
If hearth is
flush with flooring
D
iRect
V
ent
:
WARNING: This appliance has been designed to draw room air for proper heat circulation
from the sides of the unit, and out the top front. Blocking or modifying these openings in
any way can create hazardous situations.
The vent length for the E44 must be between 15ft (4.5 m) and 40ft (12 m).
This model is vented with a 3” intake and a 3” exhaust aluminum or stainless steel approved flex vent
leading into a vertical termination cap. The flue collars of this model will fit inside of a standard 3” vent
and must be fastened directly to the vent with three screws. The exhaust vent and air intake are both
located on the top of the unit.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been
properly sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must
be installed in the correct locations on the top of the E44.
20