Initial Installation
QUALIFIED INSTALLERS ONLY
22
g
as
L
ine
c
onnection
:
WARNING:
Only persons licensed to work with gas piping
may make the necessary gas connections to this
appliance.
Gas Line Connection:
• A ⅜” NPT male pipe nipple (supplied with the unit) will
have to be turned into the valve at the lower left side rear
of this fireplace (see Figures 25 and 26). Consult the local
authorities for local codes or use the CAN/CGA B149 (1 or 2)
installation code in Canada. In the US, gas installations follow
either local codes or the current edition of the National Fuel
Gas Code ANSI Z223.1.
• If the factory-built fireplace has no gas access hole(s)
provided, an access hole of 1.5 in (37.5mm) or less may be
drilled through the lower sides or bottom of the firebox in a
proper workmanship like manner. This access hole must be
plugged with non-combustible insulation after the gas supply
line has been installed.
•
A shut-off valve is not supplied with this unit but one should
be installed.
• The appliance and its shut-off valves must be disconnected
from the gas supply piping system during any pressure testing
where the pressure
exceeds
½ psig (3.45 KPa) or the valve
will be damaged.
Figure 25: ⅜” NPT Male Pipe Nipple
with Cover Attached.
Table 5: Orifice and Pressure Information.
E30G With Glass Burner & Nova Valve
Main Burner
Natural Gas
Propane Gas
Orifice:
#39 DMS
#54 DMS
Max. Manifold Press:
3.8 W.C. (0.95 KPa)
11.0 W.C. (2.74 KPa)
Min. Manifold Press:
1.2 W.C. (0.30 KPa)
2.7 W.C. (0.67 KPa)
Max. Supply Press:
10.5 W.C. (2.62 KPa)
13.0 W.C. (3.24 KPa)
Min. Supply Press:
3.5 W.C. (0.87 KPa)
8.0 W.C. (1.99 KPa)
Max. Input:
33,000 BTU/hr (9.67 KW)
28,000 BTU/hr (8.21 KW)
Min. Input:
16,500 BTU/hr (4.84 KW)
14,000 BTU/hr (4.1 KW)
Figure 26: ⅜” NPT Male Pipe Nipple
with Cover Removed.