16
Maintenance And Service
Figure 20: Pilot assembly
beside the burner.
8. Reinstall the burner, fire grate, log set, and glass door. Also refer to
S
econdary
i
nStallation
- l
oG
S
et
i
nStallation
in your Owner’s Manual. When re-installing the burner, ensure that the burner to pilot
hood and shield relationship is similar to what is shown in Figure 20.
9.
Reconnect
the main gas line if it was disconnected and open the shut-off valve at the gas line to the
unit.
10. Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap
and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by
using an approved pipe thread sealant or approved Teflon tape. NEVER USE AN OPEN FLAME WHEN
TESTING FOR LEAKS.
11. Reconnect the electrical power to the unit.
12. Relight the pilot and confirm the flame
properly covers both the thermocouple
and thermopile (see Figure 3, page 8)
.
Should the pilot require adjustment,
turn the adjustment screw (figure 38,
page 31) clockwise to decrease or
counterclockwise to increase until the
correct flame is achieved.
13.
Relight the main burner in both the
“HI” and “LO” positions to verify
proper burner ignition, operation
and proper flame appearance (figure
47, page 35). Confirm the inlet and
manifold pressures are within the
acceptable ranges as directed in
section
i
ntial
i
ntallation
- G
aS
l
ine
c
onnection
and
t
eStinG
.
If the Berkeley has been installed at an altitude higher than 2000ft
(610m) it is required to de-rate the unit accordingly and use the supplied #56 orifice on
the left (LP only):
In the USA:
The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada
: When the appliance is installed at elevations above 4500 feet (1372 m), the certified high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
14. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the unit
has been converted to a different fuel type.