12
Specifications
C
LEARANCES
T
O
C
OMBUSTIBLES
- 1700 KI I
NSERT
:
A
Minimum clearance to an unshielded side wall
10” (254 mm)
B
Minimum clearance to an unshielded 8” (203
mm) mantel
24” (610 mm)
C
Minimum top facing (protruding ¾” [19
mm]) clearance
19½” (495 mm)
D
Minimum side facing (protruding ¾” [19
mm]) clearance
1” (25 mm)
E
† From front of door opening to edge of fl oor
protection
USA 16” (406 mm)
CND 18” (450 mm)
F
† From side/back of unit to edge of fl oor
protection
USA 6” (152 mm)
CND 8” (200 mm)
†
FLOOR PROTECTION:
If unit is raised 0” - 2” (0mm-51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent.
If unit is raised 2” - 8” (51mm-203mm); ½” (13mm) non-combustible material with k value = 0.84 or equivalent.
If unit is raised greater than 8” (203 mm) or more; any non-combustible material can be used.
Table 6: Reduction in (B) Minimum Clearance from 1700 KI to 8” (203 mm) Mantel.
Type of protection
Modifi ed Clearance
A minimum of .013” (0.33mm) sheet metal spaced out 1” (25mm) by non-
combustible spacers.
12” (305 mm)
Ceramic tiles, or eqivalent non-combustible material on non-combustible
supports and spaced out 1” (25mm) by non-combustible spacers.
16⅛” (408 mm)
Ceramic tiles, or eqivalent non-combustible material on non-combustible
supports with a minimum of .013” (0.33mm) sheet metal spaced out 1”
(25mm) by non-combustible spacers.
12” (305 mm)
NOTES:
(1) Mantel protection must have at least 3” (75mm) edge clearance on all sides, except as provided in Note 4.
(2) If an adhesive is used to support non-combustible material, it shall not lose adhesive qualities at temperatures
likely to be encountered and shall not contribute a signifi cant combustible load.
(3) Heat shield mounting hardware attached to combustible materials must be placed at the lateral extremities of
the shield.
(4) Minimum clearance to unprotected walls and ceilings must be maintained.
Table 7: 1700 KI Insert Minimum Fireplace Size.
Masonry
Zero Clearance
Minimum Depth
18” (457 mm)
18½” (470 mm)
Minimum Width at back of fi replace
22⅜” (568 mm)
23” (584 mm)
Minimum Width at front of fi replace
27” (686 mm)
27¼” (692 mm)
Minimum Width at front of fi replace to include shroud
36” (915 mm)
36” (915 mm)
Minimum Height
19¼” (489 mm)**
or 19¾” (502 mm)
20” (508 mm)
**
If the masonry lintel height is only 19¼” (489 mm) to 19¾” (502 mm) refer to I
NSTALLATION
- M
ODIFICATIONS
F
OR
I
NSTALLATION
WITH
19¼” (489
MM
) H
IGH
L
INTEL
- I
NSERT
B
A
D
C
A
djac
en
t w
all
F
E
Table 5: 1700 KI Insert Clearance to Combustibles.