6.5 Menu structure
The menu structure supports the user when adjusting the measuring range, the calibration, the
measurement values and the choice of additional functions. In this connection, the numbering both on the
display and in the PC interface is identical:
1. Measurement range
Setting all relevant measuring range settings
1.1 Tag No.
Input:
Free text (10 characters)
Name of the measurement point
or product.
1.2 Unit
Selection:
m
3
, l, hl, ml, ft
3
, in
3
Desired unit for the air flow rate.
1.3 Time unit
Selection:
h, min, s
Time base for air flow calculation.
1.4 Decimal point
Selection:
Number representation and
0000, 0.000, 00.00, 000.0
decimal point-accuracy in the
measurement menu.
1.5 Set point low
Input:
0 … 9999
Measured values under this value will
not be displayed at the current output.
The display is not affected by this.
1.6 Set point high
Input:
0 … 9999
Measured values over this value will not
be displayed at the current output.
The display is not affected by this.
1.7 Filter
Input:
0.0 s … 999.9 s
Filtering of measurement for the
indicator and the output values.
1.8 Display factor
Selection:
Factor for showing higher volume
x1; x10; 10E2;....; x10E6
flow rates than 9999 m
3
/h.