
16
IP2246EN
8. Commands
Command
Function
Description
30
2
NO
AUTOMATIC
CLOSURE
The permanent closure of the contact enables automatic closure
if
→
30
3
NO
OPENING
When selecting
→
→
, the closure of the contact acti-
vates an opening operation.
STEP-BY-STEP
When selecting
→
→
, the closure of the contact
activates a sequential opening or closing operation: open-
ing-stop-closing-opening.
The “opening-stop-closing-opening” sequence can be changed
to “opening-stop-closing-stop-opening” by selecting
→
.
30
4
NO
CLOSURE
The closure of the contact activates a closing operation.
30
5 NO
STEP-BY-STEP
When selecting
→
→
, the closure of the contact
activates a sequential opening or closing operation: open-
ing-stop-closing-opening.
WARNING: if automatic closure is enabled, the duration of the
stop can be defined by selecting
→
.
The “opening-stop-closing-opening” sequence can be changed
to “opening-stop-closing-stop-opening” by selecting
→
.
OPENING
When selecting
→
→
, the closure of the contact acti-
vates an opening operation.
1
6
NC
SAFETY STOP
The opening of the safety contact stops and prevents any movement.
NB:
to set different safety contact functions, see the →
parameter settings.
1
8
NC
CLOSING
SAFETY DE-
VICE
The opening of the safety contact triggers a reversal of the move-
ment (reopening) during the closing operation.
When selecting
→
→
, the opening of the contact pre-
vents any operation when the automation is idle.
When selecting
→
→
, the opening of the contact only
prevents closure when the automation is idle.
1
6
8
NC
CLOSING/
OPENING
SAFETY DE-
VICE
The opening of the safety contact stops and prevents any move-
ment.
NB: operation corresponds to that of contact 1-6 with
→
→
.
30
9
NC
STOP
The opening of the safety contact causes the current operation to
stop.
If
-
=
,automatic closure is disabled when contact 30-9
recloses.
If
-
=
,automatic closure remains enabled when contact
30-9 recloses.
30
9
NO
"OPERATOR
PRESENT"
COMMAND
When selecting
→
→
, the opening of contact 30-9 ena-
bles the "operator present" function:
- opening with operator present 30-3
- closure with operator present 30-4
NB: any safety devices, automatic closure and plug-in board in the
AUX housing are all disabled.
30
20
NO
PARTIAL OPEN-
ING
The closure of the contact activates a partial opening operation.
Once the automation stops, the partial opening control performs the
opposite operation to the one performed before the stop.
WARNING: make a jumper for all NC contacts if not used, or deactivate them via the relative menu.
Terminals with the same number are equal.
WARNING: terminal 30 (common positive for commands) has the same functions as terminal 1, so
the commands visible on the display are indicated with 1-5, 1-3, 1-4, etc.
It is different from terminal 1, however, because of the maximum current that can be dispensed and
it is also active when the control panel is in standby
→
.
i
You are advised to read paragraph 11 for all the details about the possible adjustments.
Содержание LCU40H
Страница 6: ...6 IP2246EN A B Fig 4 5 Fig 4 3 Fig 4 4 ...