15 ANSI / BHMA A156.19 (LOW ENERGY APPLICATION)
15
ANSI / BHMA A156.19 (LOW ENERGY APPLICATION)
15.1
REQUIREMENTS FOR POWER OPERATED DOORS
The following texts are excerpts from American National Standard for power-operated
doors. Please refer to the full standard if necessary.
15.1.1
Activation
The operator shall be activated by a knowing act.
15.1.2
Opening
Doors shall open from closed to back check, or 80 degrees which ever occurs first, in 3
seconds or longer as required in Table I. Backcheck shall not occur before 60 degrees
opening. Total opening time to 90 degrees shall be as in Table II. If the door opens more than
90 degrees, it shall continue at the same rate as backcheck speed. When powered open, the
door shall remain at the open position for not less than 5 seconds.
15.1.3
Closing
Doors shall close from 90 degrees to 10 degrees in 3 seconds or longer as required in Table
I. Doors shall close from 10 degrees to fully closed in not less than 1.5 seconds.
15.1.4
Force and Kinetic Energy
The force required to prevent a stopped door from opening or closing shall not exceed 15 lbf (67
N) measured 1" (25 mm) from the latch edge of the door at any point during opening or
closing. The kinetic energy of a door in motion shall not exceed 1.25 lbf-ft (1.69 Nm).
Table I provides minimum times for various widths and weights of doors for obtaining
results complying with this kinetic energy.
Doors shall open with a manual force not to exceed 15 lbf (67 N) to release a latch, if
equipped with a latch, 30 lbf (133 N) to set the door in motion, and 15 lbf (67 N) to fully
open the door. The forces shall be applied at 1" (25 mm) from the latch edge of the door.
Table I
Minimum Opening Time to Back Check or 80 degrees, which ever occurs first, and the
Minimum Closing Time from 90 degrees to Latch Check or 10 degrees.
“D” Door Leaf Width - Inches (mm)
“W” Door Weight in Pounds (kg)
100 (45.4) 125 (56.7) 150 (68.0) 175 (79.4) 200 (90.7)
*30 (762)
3.0
3.0
3.0
3.0
3.5
36 (914)
3.0
3.5
3.5
4.0
4.0
42 (1067)
3.5
4.0
4.0
4.5
4.5
48 (1219)
4.0
4.5
4.5
5.0
5.5
* Check applicable Building Codes for clear width requirements in Means of Egress.
Содержание Ditec HA7
Страница 1: ...Installation and Service Manual Swing Door Operator Ditec HA7 Trusted brands Great products ...
Страница 13: ...6 Part identification 13 Issue 2020 08 31 1021444 2 0 6 Part identification ...
Страница 22: ...10 Mechanical installation 22 Issue 2020 08 31 1021444 2 0 ...
Страница 23: ...10 Mechanical installation 23 Issue 2020 08 31 1021444 2 0 ...
Страница 24: ...10 Mechanical installation 24 Issue 2020 08 31 1021444 2 0 ...
Страница 25: ...10 Mechanical installation 25 Issue 2020 08 31 1021444 2 0 ...
Страница 26: ...10 Mechanical installation 26 Issue 2020 08 31 1021444 2 0 ...
Страница 27: ...10 Mechanical installation 27 Issue 2020 08 31 1021444 2 0 ...
Страница 29: ...10 Mechanical installation 29 Issue 2020 08 31 1021444 2 0 ...
Страница 30: ...10 Mechanical installation 30 Issue 2020 08 31 1021444 2 0 ...
Страница 31: ...10 Mechanical installation 31 Issue 2020 08 31 1021444 2 0 ...
Страница 32: ...10 Mechanical installation 32 Issue 2020 08 31 1021444 2 0 ...
Страница 33: ...10 Mechanical installation 33 Issue 2020 08 31 1021444 2 0 ...
Страница 34: ...10 Mechanical installation 34 Issue 2020 08 31 1021444 2 0 ...
Страница 37: ...11 Electrical connection 37 Issue 2020 08 31 1021444 2 0 11 2 Control unit CU ...
Страница 41: ...12 Start up 1021444 2 0 Issue 2020 08 31 41 12 2 4 Test 12 2 5 Settings ...
Страница 42: ...42 Issue 2020 08 31 1021444 2 0 12 Start up 12 2 6 Add user 0 12 2 7 Remove user ...
Страница 49: ......