Data Clock Output
The following figure shows how to cable the wires of the Wiegand OUT port of the
terminal for Data Clock protocol. This is used, for instance, to connect the
MorphoAccess® SIGMA Lite terminal to an Access Control Panel (ACP).
Figure 17: Wiegand port wiring – Data Clock
14 Green
WIEGAND _OUT0
Out
Data ( 5V TTL )
16 White
WIEGAND _OUT1
Out
Clock ( 5V TTL )
17 Blue
WIEGAND_LEDOUT1 In
Card present signal (if
configured, only one selectable
for Morpho Legacy)
18 Blue / Red
WIEGAND_LEDOUT2 In
Card present signal (if
configured)
20 Black / Red
WIEGAND_GND
Ground for Wiegand
www.TURNSTILES.us / www.entrapass.com / 8641 S. Warhawk Road, Conifer, CO 80433 / 303-670-1099